Catalog
Overview I/O module TXM1..
Product TXM1.8D TXM1.16D TXM1.8U TXM1.6R TXM1.6RL TXM1.8RB TXM1.8T
Number of inputs/outputs 8 16 8 6 6 8 8
Functionality
3-color I/O status LED ⦁
Green I/O status LED ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Digital inputs (DI)
Message signal (open/closer) ⦁ ⦁ ⦁
Message impulse ⦁ ⦁ ⦁
Counter 25 Hz (bouncer free)
⦁
*
⦁
Analog inputs (AI)
LG-Ni1000 ⦁
Pt1000 / 0...2500 Ohm ⦁
T1 ⦁
DC 0...10 V ⦁
Analog outputs (AO)
DC 0...10 V ⦁
Digital outputs (DO)
Continuous contact on/off ⦁ ⦁
Continuous contact 3-stage ⦁
3-point output (stroke model) ⦁ ⦁
Impulse on/off ⦁
Impulse ⦁
Impulse 3-stage ⦁
Bistable contact ⦁
Contact for control of blinds ⦁
Modulating (PWM) ⦁
All I/O points of a module are configurable on any implemented functionality. The module TXI1.OPEN enables the integration of Modbus, M-bus, etc.
on the PXC50/100/200..D.
* On the TXM1.16D the counters are implemented only on the inputs 1 to 8
Compact room automation station with BACnet
Communication
BACnet/IP DXR2.
E09-101A
DXR2.
E09T-
101A
DXR2.
E10-101A
DXR2.
E12P-
102A
DXR2.
E18-1..A
DXR2.
E10PL-
102B
DXR2.
E10PLX-
102B
DXR2.
E17C-
103A
DXR2.
E17CX-
103A
BACnet
MS/TP
DXR2.
M09-
101A
DXR2.
M09T-
101A
DXR2.
M10-
101A
DXR2.
M11-
101A
DXR2.
M12P-
102A
DXR2.
M18-1..A
DXR2.
M10PLX-
102B
System functions (BACnet)
BACnet profiles B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC
Programming ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Housing
DIN ⦁ ⦁ ⦁ ⦁ ⦁
Flat ⦁ ⦁ ⦁ ⦁* ⦁*
Operating voltage
230 V ⦁ ⦁ ⦁
24 V ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Inputs and outputs onboard
Digital inputs 1 1 1 1 1 2 1 1 2 2
Universal inputs 2 2 2 2 2 4 2 2 4 4
Relay outputs 3 1 3
Triac outputs 4 4 6 6 8 4 4 4 4
Analog outputs
(DC 0…10 V)
3 1 2 2 4 1 1 4 4
Pressure sensor 1
Maximum configuration
Total data points 30 30 30 30 30 60 30 60 30 60
Integrated power
supply for KNX (mA)
50 50 50 50 50 50 50 50 50 50
* Via damper
4–22
4–23
1 1
3
2
3
2
4 4
Room automation
Overview and selection tools
Room automation
Overview and selection tools