Overview I/O module TXM1..
Product TXM1.8D TXM1.16D TXM1.8U TXM1.6R TXM1.6RL TXM1.8RB TXM1.8T
Number of inputs/outputs 8 16 8 6 6 8 8
Functionality
3-color I/O status LED
Green I/O status LED
Digital inputs (DI)
Message signal (open/closer)
Message impulse
Counter 25 Hz (bouncer free)
*
Analog inputs (AI)
LG-Ni1000
Pt1000 / 0...2500 Ohm
T1
DC 0...10 V
Analog outputs (AO)
DC 0...10 V
Digital outputs (DO)
Continuous contact on/off
Continuous contact 3-stage
3-point output (stroke model)
Impulse on/off
Impulse
Impulse 3-stage
Bistable contact
Contact for control of blinds
Modulating (PWM)
All I/O points of a module are configurable on any implemented functionality. The module TXI1.OPEN enables the integration of Modbus, M-bus, etc.
on the PXC50/100/200..D.
* On the TXM1.16D the counters are implemented only on the inputs 1 to 8
Compact room automation station with BACnet
Communication
BACnet/IP DXR2.
E09-101A
DXR2.
E09T-
101A
DXR2.
E10-101A
DXR2.
E12P-
102A
DXR2.
E18-1..A
DXR2.
E10PL-
102B
DXR2.
E10PLX-
102B
DXR2.
E17C-
103A
DXR2.
E17CX-
103A
BACnet
MS/TP
DXR2.
M09-
101A
DXR2.
M09T-
101A
DXR2.
M10-
101A
DXR2.
M11-
101A
DXR2.
M12P-
102A
DXR2.
M18-1..A
DXR2.
M10PLX-
102B
System functions (BACnet)
BACnet profiles B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC B-ASC
Programming
Housing
DIN
Flat * *
Operating voltage
230 V
24 V
Inputs and outputs onboard
Digital inputs 1 1 1 1 1 2 1 1 2 2
Universal inputs 2 2 2 2 2 4 2 2 4 4
Relay outputs 3 1 3
Triac outputs 4 4 6 6 8 4 4 4 4
Analog outputs
(DC 0…10 V)
3 1 2 2 4 1 1 4 4
Pressure sensor 1
Maximum configuration
Total data points 30 30 30 30 30 60 30 60 30 60
Integrated power
supply for KNX (mA)
50 50 50 50 50 50 50 50 50 50
* Via damper
4–22
1 1
3
2
3
2
4 4
Room automation
Overview and selection tools
Room automation