Catalog

Preloaded applications
Pressurized rooms and fume hoods
Desigo room pressurization and fume hood control is a range of dedicated,
reliable air volume flow controllers and supplementary components for
secure, precise and fast measurement, control and monitoring of air
volume flows and room pressures in highly specialized working spaces.
It is part of the Desigo building automation and control system.
As a result, the overall system maximizes security, efficiency and cost-
effectiveness.
Locations:
Highly specialized research and manufacturing spaces requiring
dedicated high-speed control solutions for room pressurization & fume
hood control
Rooms in:
Research facilities
Pharma/Biotech
Healthcare
Hi-tech manufacturing
Vivariums
Higher education customers, etc.
Applications:
Room ventilation and general extraction, measuring, controlling and
monitoring of air volume flows
Room balancing and room pressurization control
Laboratory fume hood air volume flow control and monitoring
Room air conditioning together with lighting & shading control
Room and fume hood emergency functions
Demand-controlled ventilation support for energy-saving opportunities
Pressurized rooms and fume hoods
Application works self-contained or distributed across multiple
automation stations.
1 room segment control (30 data points)
operates one supply and one extract terminal or one fume hood,
as well as coordinates operation among multiple room segments.
2 room segment control in single automation station
(60 data points)
operates two supply and two extract terminals or one fume hood,
as well as coordinates operation among multiple room segments.
Variable (VAV) and constant volume flow
with 2-stage electric heating
with hot water
with hot water and flow temperature control
with hot water and thermal power control
Separate temperature and volume set points for all 4 operating modes.
Supply and extract air flow tracking
Room pressure cascade control
Accepts external demand control ventilation signal
Chilled water and hot water valve
Chilled beam active or passive cooling (2-pipe) or cooling/heating
(2-pipe) or cooling/heating (4-pipe)
Radiant ceiling: cooling, cooling and heating (2-pipe) or cooling/heating
(4-pipe)
Radiator: hot water, steam (2- or 4-pipe) or electric stepped controlled
Light: up to 4 separate zones
Blinds: 1 or 2 motors
Primary air
temperature
for air after-
treatment
(TPaAftrt)
Supply air
VAV differen-
tial pressure
(VavSuDiffP)
Cooling coil
(Ccl)
Heating/
cooling coil
(HCcl)
Heating coil
(Hcl)
Supply air
temperature
(TSu)
Extract air
temperature
(TEx)
Extract air
VAV differen-
tial pressure
(VavExDiffP)
BI (Ohm) 1 1 1
DI
AI
(0…10 V)
1 1 1
AI
(0…20 mA)
1 1
Triac 1 1 1
AO (0…10 V) 1 1 1
1
1
SCOM 1 1 1
1
1
Preloaded applications
Fume hood exhaust damper control
Sensors (face velocity, duct exhaust flow, sash position)
Operator display panel
Push buttons, switches for fume hood lighting
1 light
4–16
1 1
3
2
3
2
4 4
Room automation
Overview and selection tools
Room automation