Catalog

HVAC applications
Application types
Fan coil
Application can be configured from these functions:
Outside air damper
Single-speed fan, multi-speed fan or variable-speed fan
Chilled water cooling coil
Direct expansion evaporator cooling coil
Heating/cooling coil
Hot water heating coil
Electric heating coil modulating, single stage or 2 stage
Room temperature control by 2-pipe system with changeover
Room temperature control by 4-pipe system
Supply air temperature cascade control
Room dehumidification control
Air volume flow control
Rapid ventilation
Green Leaf
Frost protec-
tion monitor
(FrPrtMon)
Outside air
damper
(DmpOa)
Extract air
tempera-
ture (TEx)
Mixed air
tempera-
ture (TMx)
Fan speed
(FanSpd)
Cooling
coil (Ccl)
Heating/
cooling coil
(HCcl)
Heating
coil (Hcl)
Supply air
tempera-
ture (TSu)
DI 1
AI 1 1 1
Relais 1–3
Triac 2 1–2 1–2 1, 2, 4 ,8 1–2
0..10 V 1 1* 1 1, 4 1**
* Requires additional relais or triac for enable signal
** Requires additional triac for electric heating enable signal
VAV (variable air volume system)
Application can be configured from these functions:
Supply and extract air control
External flow control for VAV with integrated flow controller
and differential pressure sensor
Internal flow controller and differential pressure sensor for
damper actuator control
Internal flow controller and velocity sensor for damper actuator control
Chilled water cooling coil
Heating/cooling coil
Hot water heating coil
Electric heating coil modulating, single stage or 2 stage
Room temperature control by 2-pipe system with changeover
Room temperature control by 4-pipe system
Supply air temperature cascade control
Air flow tracking for under/overpressure
Room dehumidification control
Room air quality control
Rapid ventilation
Green Leaf
Primary air temperature
for air after treatment
(TPaAftrt)
Supply air
VAV
(VavSu)
Cooling
coil (Ccl)
Heating/
cooling coil
(HCcl)
Heating
coil (Hcl)
Supply air
temperature
(TSu)
Extract air
temperature
(TEx)
Extract air
VAV
(VavEx)
DI
AI 1 1 1
Relais
Triac 2** 1–2 1, 2, 4 ,8 1-2 2**
0..10 V 1 1 1, 4 1* 1
Actuator for VAV
(KNX PL-Link)
1 1
* Requires additional triac for electric heating enable signal
** When using DXR2.. with AC 24 V power supply in combination with GDB181.1E/3 or GLB181.1E/3, use 0..10 V signals.
Fan powered box
Application can be configured from these functions:
Supply air control
External flow control for VAV with integrated flow controller and
differential pressure sensor
Internal flow controller and differential pressure sensor for damper
actuator control
Internal flow controller and velocity sensor for damper actuator control
Single-speed fan, 2-speed fan or variable-speed fan
Chilled water cooling coil
Heating/cooling coil
Hot water heating coil
Electric heating coil modulating, single stage or 2 stage
Room temperature control by 2-pipe system with changeover
Room temperature control by 4-pipe system
Supply air temperature cascade control
Room air quality control
Rapid ventilation
Green Leaf
Primary air tempera-
ture for air after-
treatment (TPaAftrt)
Supply air
VAV
(VavSu)
Extract air
tempera-
ture (TEx)
Mixed air
tempera-
ture (TMx)
Fan speed
(FanSpd)
Cooling
coil (Ccl)
Heating/
cooling
coil (HCcl)
Heating
coil (Hcl)
Supply air
tempera-
ture (TSu)
DI
AI 1 1 1 1
Relais
Triac 2 1–2 1–2 1, 2, 4, 8 1–2
0..10 V 1 1* 1 1, 4 1**
Actuator for VAV
(KNX PL-Link)
1*
* Requires additional triac for enable signal
** Requires additional triac for electric heating enable signal
Radiant ceiling and radiator
Application can be configured from these functions:
Chilled ceiling with chilled water
Heated/chilled ceiling by 2-pipe system with changeover
Heated/chilled ceiling by 4-pipe system with 6 way valves
Heating ceiling with hot water
Hot water radiator
Electric radiator modulating or staged
Downdraft compensation for radiators
Condensation monitor
Room temperature control
Green Leaf
Radiator
(Rad)
Radiator
overtemperature
(RadOvrT)
Radiant ceiling
(Rcg)
Condensation monitor
(CdnMon)
DI 1 1
AI
Relais
Triac 1–4 1–4
0..10 V 1–2* 1–2
* Requires additional triac or relais for electric heating enable signal
4–8
1 1
3
2
3
2
4 4
Room automation
Overview and selection tools
Room automation
Overview and selection tools