Catalog
Application configuration
Applications can be configured by combining functions from one or several application types:
• Room sensor and operating
• Radiant (heated/chilled) ceiling and radiator
• Fan coil
• VAV system or fan-powered box
• Lighting
• Shading
Configuration is limited by total number of data points.
Application group central functions requires dedicated room automation station.
Configurable controllers
Communication
BACnet/IP DXR2.
E09-
101A
DXR2.
E09T-
101A
DXR2.
E10-
101A
DXR2.
E12P-
102A
DXR2.
E12PX-
102A
DXR2.
E18-
101A
DXR2.
E18-
102A
DXR2.
E10PL-
102B
DXR2.
E10PLX-
102B
DXR2.
E17C-
103A
DXR2.
E17CX-
103A
BACnet MS/TP DXR2.
M09-
101A
DXR2.
M09T-
101A
DXR2.
M10-
101A
DXR2.
M11-
101A
DXR2.
M12P-
102A
DXR2.
M18-
101A
DXR2.
M18-
102A
DXR2.
M10PL-
102B
DXR2.
M10PLX-
102B
Application types
Room operating ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Heated / chilled
ceiling and radiator
⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Fan coil ⦁ ⦁ ⦁ ⦁ ⦁
VAV system or
fan-powered box
⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Pressurized and
fume hood
⦁ ⦁
Lighting ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Shading ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Central functions ⦁* ⦁*
Housing
DIN ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Flat ⦁ ⦁ ⦁ ⦁** ⦁**
Operating voltage
230 V ⦁ ⦁ ⦁
24 V ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁ ⦁
Inputs and outputs onboard
Resistor inputs 0 0 0 0 0 0 0 0 0 2 2
Digital inputs 1 1 1 1 1 1 2 2 1 1 2 2
Universal inputs 2 2 2 2 2 2 4 4 2 2 4 4
Relay outputs 3 1 3
Triac outputs 4 4 6 6 6 8 8 4 4 4 4
Analog outputs
(DC 0…10 V)
3 1 2 2 2 4 4 1 1 4 4
Pressure sensor 1 1 1 1
SCOM communica-
tion for sensors
⦁ ⦁
Maximum configuration
Total data points 30 30 30 30 30 60 60 60 30 60 30 60
Integrated power
supply for KNX
(mA)
50 50 50 50 50 50 50 50 50 50
* Cannot be combined with other applications ** Via damper
Example of product selection
1. Check application requirements
Requirements
• Fan coil
• 4-pipe system
• 3-speed fan
• 2 valves with electrothermal actuators (2-point control signal)
• Voltage AC 230 V
• Presence detector
• Room unit with built-in temperature sensor
Frost
protection
(FrPrtMon)
Outside air
damper
(DmpOa)
Extract air
tempera-
ture (TEx)
Mixed air
tempera-
ture (TMx)
Fan speed
(FanSpd)
Cooling
coil (Ccl)
Heating/
cooling coil
(HCcl)
Heating
coil (Hcl)
Supply air
tempera-
ture (TSu)
DI
AI
Relais 3
Triac 1 1
0..10 V
Relais + 0..10 V
2. Find matching products in overview tables
Products matching application requirements above:
Product Number Description Qty
DXR2.E10 Compact room automation stations, BACnet/IP, 230 V 1
QMX3.P34 Room operator unit KNX with temperature sensor, segmented backlit display, touchkeys 1
UP 258D11 Passive infrared presence detector 1
STP73 Electrothermal actuator, AC/DC 24 V, NO, 2P, 1 m 2
VMP47.10-1.6 3-port seat valve with bypass, external thread, PN16, DN10, kvs 1.6 2
Note:
Product overview tables provide quick overview and show main features; nevertheless,
we recommend checking technical parameters of each product.
3. Check total data points and bus load
Used DXR2.. onboard data points: 5
KNX PL-Link data points: 5
Total used data points: 10 < 30
Total KNX PL-Link bus load: 17.5 mA < 50 mA
Correct, total values do not exceed maximum configuration.