Catalog

Overview of automation stations:
Modular series
BACnet/IP PXC00-E.D PXC50-E.D PXC100-E.D PXC200-E.D
BACnet/LonTalk PXC00.D PXC50.D PXC100.D PXC200.D
Number of data points via
TX-IO modules
Up to 52 Up to 200 Over 200
Number of TX Open
modules for e.g. Modbus,
M-Bus
5 5 5
Number of LonWorks
devices via PXX-Lx
60 or 120 10 60
1)
or 120
1)
60
1)
or 120
1)
1) In concurrent use with TX-I/O modules, the number of devices can be reduced in relation to capacity
Overview of automation stations:
Compact series
BACnet/LonTalk PXC12.D PXC22.D PXC22.1.D PXC36.1.D
BACnet/IP PXC12-E.D PXC22-E.D PXC22.1-E.D PXC36.1-E.D
I/Os onboard 12 22 22 36
UIO 8 16 16 24
DI 2 0 0 4
DO 2 6 6 8
Number of I/Os via TX-I/O
modules
16 16
Number of TX Open
modules
5 5
System controller PX Open
Type PXC001.D
PXC001-E.D
PXA40-RS1 PXA40-RS2
Interfaces
KNX
Serial RS232
Serial RS485
Network functions
Integration KNX 2000 DP
Integration M-Bus 250 DP 800 DP 2000 DP
Integration Modbus 250 DP 800 DP 2000 DP
Integration SCL 250 DP 800 DP 1000 DP
TX Open RS232/485 module
Type Description
TXI2.OPEN TX Open RS232/485 module (up to 160 data points)
TXI2-S.OPEN TX Open RS232/485 module (up to 40 data points)
PXC100.D
PXC36.1-E.D
PXC001.D
TXI2.OPEN
Remote IO Islands with integration
Type Description
TXA1.IBE Easy-to-use solution with as simple adapter for remote TX-IO and TX Open.
No programming/parameterization required
TXA1.IBE
Overview TX-I/O™ module range TXM1..
Type
TXM1.8D
TXM1.16D
TXM1.8U
TXM1.8U-ML
TXM1.8X
TXM1.8X-ML
TXM1.6R
TXM1.6R-M
TXM1.8P
TXM1.6RL
TXM1.8T
Number of I/Os 8 16 8 8 8 8 6 6 8 6 8
Functionality
Local operation
LC-Display
3-color I/O status LED
Green I/O status LED
Digital inputs (DI)
Message signal (open/closer)
Message impulse
Counter 10 Hz (with debouncing)
1-8
1)
Counter 25 Hz (bouncer free)
Analog inputs (AI)
LG-Ni1000
Pt 1000 / 0...2500 Ohm
T1
DC O...10 V
3)
4...20 mA / 0...20 mA
4)
Analog outputs (AO)
DC 0...10 V
4...20 mA 5–8
2)
5–8
2)
Digital outputs (DO)
Continuous contact on/off
Continuous contact, 3-stage
3-stage output
Impulse on/off, 3-stage
Multistate
Triac-continuous contact
Triac-impulse (3-stage)
Triac pulsewidth-modulated
Light control, bistable
1) On the TXM1.16D the counters are implemented only on the inputs 1 to 8
2) On the TXM1.8X.. the current exists 4...20 mA are implemented only on the I/Os 5 to 8
3–4
1 1
2
44
2
3 3
Automation controls
Overview and selection tools
Automation controls
Overview and selection tools