User Guide

Alarms
Working with Alarms
3
73 | 393
Siemens
User Guide Version 3.0
A6V10415471
Building Technologies
2017-11-30
operating procedure. See Completing an Operating Procedure of Assisted
Treatment [➙ 73].
Wait for condition. The event cannot be reset until the event source
is back to normal. You must correct the situation that caused the alarm, or
wait for the event source to return to the Quiet state, before you can finish
handling this event.
Reset event. In the Commands column, click Reset .
Close event. In the Commands column, click Close .
Suspend the event. You finished handling this event, and the event is
ready to be cleared from the list. Click the event button again to deselect
the event. It will then be removed from Event List.
3. While handling the alarm according to the Suggested action, also check the
Command column for any other, optional commands available to you. These
may include:
After you acknowledge an event, if the alarm has caused a field panel to
sound an audible alarm in the site, click Silence to silence the panel,
or click Unsilence to turn it back.
If any remote notification is configured for that event, Start Remote
Notifications or Stop Remote Notifications become available.
4. To stop handling the event click the event button again.
The Assisted Treatment window closes. The event is cleared from Event List.
Related Topics
Event Descriptor Reference [➙ 102]
Interrupting Handling of an Alarm [➙ 80]
Alarm-Handling Commands Reference [➙ 109]
Event Status and Suggested Action Reference [➙ 110]
3.1.6.3 Completing an Operating Procedure of Assisted Treatment
You are handling an event from the Assisted Treatment window.
The Suggested action is Complete Operating Procedure, no further
commands are available because you must first complete at least the
mandatory steps of the operating procedure. Mandatory steps are marked with
an exclamation mark .
1. Move your cursor over a step.
If it turns into a hand , it means you can execute that step.
If it turns into a pointer , it means that you cannot execute that step. This
is usually because a preceding mandatory step needs to be completed first.
In this case, try another step.