User Guide
Organization Modes
Manually Setting an Organization Mode
12
374 | 393
Siemens
User Guide Version 3.0
A6V10415471
Building Technologies
2017-11-30
12 Organization Modes
This section provides background information and instructions for using
Organization Modes in Desigo CC.
12.1 Manually Setting an Organization Mode
Scenario: You want to manually change the value of the Day and Night
organization mode from Day to Night.
1. In System Browser, select Management View.
2. Select Project > System Settings > Organization Modes.
3. From the Organization Modes folder, select Day and Night.
In the Operation tab, the Value parameter displays the current value of the
organization mode.
4. From the drop-down list, select Night.
5. Click Set.
The Value parameter is saved with the new setting.
Related Topics
Organization Modes Reference [➙ 374]
12.2 Organization Modes Reference
Organization modes are system objects that can reflect the operational status or
schedule of the building control site (for example, whether the facility is open or
closed, its occupancy status, whether it is day or night, and so on).
● Organization modes are used as inputs that combined with other conditions
can trigger a variety of automated functions. For example, to trigger reactions,
automated handling of alarms, operating procedures, or graphic animations.
● Organization modes are typically set by automated logic (for example, as a
result of a schedule or reaction). But they can also be toggled manually by the
operator.
● The system comes with some predefined organization modes, but you can also
configure additional ones.
In Operating mode, you can view existing organization modes, manually toggle
their state, or create schedules to automatically set them. For related procedures,
see Working with Organization Modes.
Location of Organization Modes
Organization mode objects are accessed in the Management View of System
Browser, under Project > System Settings > Organization Modes.