User Guide

Reports
Reports Reference
8
333 | 393
Siemens
User Guide Version 3.0
A6V10415471
Building Technologies
2017-11-30
PDF document
generated for
operating procedure
does not display any
data.
Data is not
available as per
the filters applied
to the configured
table.
Graphics is not
available for the
object in the
event.
Check and correct the
applied filters.
Create a graphics
containing the object in
the event.
To create a graphics,
see Creating a Graphic.
The report for the
operating procedure
cannot get routed to
the specified printer.
Printer is faulty.
Printer is out of
paper.
Printer is
jammed.
Printer is not
available.
Printer is offline
Printer door is
open.
Rectify the printer
related issues.
The report for the
operating procedure
cannot get routed to
the specified folder.
You do not have
permissions for
the specified
folder.
Either contact the
system administrator to
receive the required
permissions on the
configured folder or
configure a new folder.
Table in the report
does not display any
data.
The Report
Definition has an
invalid condition
filter.
Ensure that the
Condition filter is
applied properly.
For steps to apply
the Condition filter
to a table, see
Applying a
Condition filter.