User Guide
Reports
Reports Reference
8
333 | 393
Siemens
User Guide Version 3.0
A6V10415471
Building Technologies
2017-11-30
PDF document
generated for
operating procedure
does not display any
data.
● Data is not
available as per
the filters applied
to the configured
table.
● Graphics is not
available for the
object in the
event.
● Check and correct the
applied filters.
● Create a graphics
containing the object in
the event.
To create a graphics,
see Creating a Graphic.
The report for the
operating procedure
cannot get routed to
the specified printer.
● Printer is faulty.
● Printer is out of
paper.
● Printer is
jammed.
● Printer is not
available.
● Printer is offline
● Printer door is
open.
● Rectify the printer
related issues.
The report for the
operating procedure
cannot get routed to
the specified folder.
● You do not have
permissions for
the specified
folder.
● Either contact the
system administrator to
receive the required
permissions on the
configured folder or
configure a new folder.
Table in the report
does not display any
data.
● The Report
Definition has an
invalid condition
filter.
● Ensure that the
Condition filter is
applied properly.
● For steps to apply
the Condition filter
to a table, see
Applying a
Condition filter.