User Guide
Reports
Reports Reference
8
290 | 393
Siemens
User Guide Version 3.0
A6V10415471
Building Technologies
2017-11-30
report. When you select an object from System Browser, this standard report
displays as a link in the Related Items.
● Date/time in UTC format check box
Selecting this check box, the date and time you type is represented in UTC
format. The following elements in Reports display date/time values:
– Keywords (Date, Time, Report Start, Report Stop, Content Start, Content
Stop)
– Columns of the tables
- Source Time column (Activities)
- Alert time and Transition time (Events)
- Creation date time (Active Events)
- Date
- Alert time and Alert went (for parent record of Event Details
- Time (for child record of Event Details)
- Event Stamp Fault, Event Stamp Off-Normal and Event Stamp Normal
(BACnet Event Information)
– Time filter dialog box
– Condition filter dialog box (Data in the reports can be filtered based on data
time values)
● Fixed Locale check box
Selecting this check box and a locale from the corresponding list, displays the
date/time and decimal separator according to the format set for the locale on
the server. For example, if you select English-US as the locale, the date/time
and decimal separator set for English-US on the server displays in the report.
8.2.6 Reports Ribbon — Filter Tab
The Filter tab allows you to define and apply different filters for data retrieval.
Figure 25: Filter Tab
The various filters are:
● Name Filter
● Condition Filter
● Time Filter
● Row Filter: Allows you to set the maximum number of rows of a table to be
displayed at runtime.
● Languages Filter: Allows you to set the language for a Report Definition. You
can configure filters (Condition and Name) in the selected language.
8.2.6.1 Name Filter
The Name filter allows you to filter data based on the Name or Description of
System Browser objects. You can apply a Name filter to a table or plot.
When an Activities, Events, Active Events, BACnet Alarm Summary, BACnet
Enrollment Summary, BACnet Event Information, and/or Objects table is inserted
in the Report Definition, a valid Name filter “CurrentSystemName.*:*” is added by
default, where CurrentSystemName is the name of the system in which report
definition is created or opened. This default Name filter can be replaced with a * to
fetch the data from all the views of all the configured systems in a distributed
environment. You can add Name filters from the Name Filter dialog box.