User Guide
Alarms
Alarms and Event Treatment Reference
3
111 | 393
Siemens
User Guide Version 3.0
A6V10415471
Building Technologies
2017-11-30
Closed
Suspend the
event
-
You reset the
event, and the
source status is
back in normal
condition. You can
clear the event.
You closed the
event and now you
can clear it.
Acknowledgment Models for Station-based Alarms
The following acknowledgment models are for station-based alarms:
● ACK and Reset required
● No Reset (ACK only required)
● No ACK, No Reset
Fast/Investigative Treatment Workflow
Acknowledgment Model
Scenario
Event Status
ACK and Reset required
● Alarm handling started (and at least
one alarm-handling command sent)
● Event source back to Quiet
Unprocessed
Waiting for
condition
Ready to be closed
Closed
● Alarm handling not started yet (no
alarm-handling command sent yet)
● Event source back to Quiet
Unprocessed
Ready to be closed
Closed
No Reset (ACK only required)
● Alarm handling started (and at least
one alarm-handling command sent)
or not started yet (no treatment
command sent yet)
● Event source back to Quiet
Unprocessed
Waiting for
condition
Closed
No ACK, No Reset
● Alarm handling started (and at least
one alarm-handling command sent)
or not started yet (no alarm-
handling command sent yet)
● Event source back to Quiet
Waiting for
condition
Closed
Assisted Treatment (with Mandatory Steps) Workflow
Acknowledgment Model
Scenario
Event Status
ACK and Reset required
● Alarm handling started (and at least
one alarm-handling command sent)
● Event source back to Quiet
Unprocessed
Waiting for
condition
Ready to be reset
Waiting for
condition (due to
mandatory steps)
Ready to be closed
Closed
● Alarm handling not started yet (and
no alarm-handling command sent
yet)
● Event source back to Quiet
Unprocessed
Ready to be reset
Waiting for
condition (due to
mandatory steps)
Ready to be closed
Closed