Visibility of Alarms and Commands
● You cannot handle events generated by field points for which you do not have
proper user privileges. Such alarms and the related commands will not be
visible to you in Event List.
● While handling events, your ability to acknowledge, reset and/or
silence/unsilence an individual field point/panel (sending an individual
command) or all the panels belonging to the same network (sending block
commands) depends on configuration.
● If you try to send block commands while an event filter is active, a message
displays asking you to remove the filter. Deactivate the filter and send the
(block) command.
● To execute Acknowledge, Reset, or Silence/Unsilence, you must have proper
user privileges, or the client station you’re working on must be the owner of the
field panel.
3.2.1.11 Event Status and Suggested Action Reference
Event Status
Suggested Action
Icon in event
button
Fast / Investigative
Treatment
Assisted
Treatment
Unprocessed
Acknowledge
event
The event is new and still unprocessed.
This means that you either did not yet
select the event, or that you selected it
but did not acknowledge it yet.
Ready to be
reset
Reset event
Not applicable
In Assisted
Treatment, you
selected an event
and the source
status is back in
normal condition.
The Reset
command is
available.
Ready to be
closed
Reset event
You selected an
event and the
Reset command
is available.
You reset an
event, and all the
mandatory steps
of the assisted
procedure were
executed. The
Close command
is available.
Waiting for
condition
Wait for
condition
You acknowledged
the event, but
cannot reset it yet.
-
Complete
Operating
Procedure
-
You acknowledged
the event, but
cannot reset it yet
because you must
first complete all
the mandatory
steps of the
assisted
procedure.