Operating Instructions

3
23
Siemens Desigo™ CC Getting Started
A6V10415475_en_a_21
Building Technologies 2015-06-30
2. Click Acknowledge .
The event is acknowledged, and the event status changes to either
Waiting for condition or Ready to be closed.
3. If the below commands are available, do one or both of the following;
otherwise, proceed to Step 4:
Click Silence , to silence the field panel.
Click Start Remote Notifications , to manually send a remote
notification message.
4. To investigate the cause of the alarm, do the following:
In the Primary pane, check any content associated to the point in alarm (for
example, a graphic).
If the event status is Waiting for condition, do whatever is
necessary to clear the physical conditions that caused an alarm.
If necessary, click a Related Item link to open it in the Secondary pane, and
perform the required action (for example, click a document link to view
instructions).
Once the event status is Ready to be closed, the suggested action is
Reset event, and the Reset command becomes available.
5. Click Reset .
The event is reset, the event status becomes Closed, and the suggested
action is Suspend event.
6. In the Investigative Treatment window, click the event button.
The Investigative Treatment window closes and the event is cleared from the
Event List.
3.2.3 Using Assisted Treatment
The following procedure is available in place of Investigative Treatment for
situations where the operator must follow a specified sequence of steps to
completely process and respond to an event. For example, such a procedure might
include the following steps:
View instructions or other important information contained in a document file or
Web page.
Check a graphic of the area where the event occurred.
Send important event detail information using the remote notification message.
Print details of the event.
Generate and print a report.
Fill out an event treatment report.
An alarm occurs in the system, the event lamp relating to its category flashes in
the Summary Bar, and a new event button appears and flashes in the Event
List. The event status is Unprocessed, and the suggested action is Select
the event.
1. In Event List, double-click the event button, for example: .
The Assisted Treatment window displays in the work area, with the event
details and treatment commands (Acknowledge, Reset, and so on) along