Events
Handling Events
22
Siemens Desigo™ CC Getting Started A6V10415475_en_a_21
Building Technologies 2015-06-30
3.2.1 Using Fast Treatment
The following procedure is recommended when handling an alarm that only
requires sending specific commands. No further investigation or control action is
required.
An alarm occurs in the system, the event lamp relating to its category flashes in
Summary Bar, and a new event button appears and flashes in Event List. The
event status is Unprocessed, and the suggested action is Select the
event.
1. In Event List, click the event button, for example: .
The event descriptor for the selected event appears highlighted to indicate
that you have selected and started to handle this event. The event status is
Unprocessed, the suggested action is Acknowledge event, and the
acknowledge command becomes available.
2. Click Acknowledge .
The event is acknowledged, and the event status changes to either
Waiting for condition or Ready to be closed. If it is Waiting
for condition, wait until the physical conditions that caused the alarm
are resolved and you can reset the field panel. Once the event status is
Ready to be closed, the suggested action changes to Reset event,
and the Reset command becomes available.
3. If the below commands are available in the event descriptor, do one or both of
the following; otherwise, proceed to the last step of the procedure:
Click Silence , to silence the field panel.
Click Start Remote Notifications , to manually send a remote
notification message.
4. Click Reset .
The event is reset, the event status becomes Closed, and the suggested
action is Suspend event.
5. In Event List, click the event button.
The event is cleared from Event List.
3.2.2 Using Investigative Treatment
The following procedure is recommended instead of Fast Treatment when handling
an alarm that requires investigation to determine its cause.
An alarm occurs in the system, the event lamp relating to its category flashes in
Summary Bar, and a new event button appears and flashes in Event List. The
event status is Unprocessed, and the suggested action is Select the
event.
1. In Event List, double-click the event button, for example: .
The Investigative Treatment window displays in the work area. The
corresponding event source point is highlighted in System Browser, while
Operation/Extended Operation displays the properties related to the point,
and Related items any of the related-objects associated to the point.