Installation Instructions

Siemens Industry, Inc.
Smart Infrastructure
P/N 315-099458-1014
12345
910111213
17 18 19 20 21
ONE SLOT OF CC-5 #
INSTALLED
AAABB
++
--+
AB
++
234567 8
10 11 12 13 14 15 16
17 18 19 20 21 22 23 24
ONE SLOT OF CC-5 #1 WITH HUB-4
INSTALLED
AA ABB BB
+
--++
--
AABB
++
--
TB1
TB2
LLM-1
12 34
12 34
AABB
++
--
ABB
+
--
MODEM OR
OR RS-485
INTERFACE
Port #3
MODEM OR
OR RS-485
INTERFACE
Port #4
MODEM OR
OR RS-485
INTERFACE
Port #2
120 OHM EOL (For use with RS-485 only)
120 OHM EOL
2.
Positive or negative ground fault detected <5K ohms
on CC-5 1-16
4.
RS-485 Ratings
Maximum current: 150mA
Maximum voltage: 8Vp-p
14-18AWG Twisted pair or twisted shielded pai
200 ohms per pair (LLM-1 not included)
0.34uF max line to line
3.
Power limited to NFPA 72 per NEC 760
P/N 140-049099
P/N 140
* The LLM-1 inserts
10 ohms between
TB1 and TB2
terminals 2 and 3 (20
ohms total).
*
6.
For more information, refer to the RS485 Interface
Installation Instructions, P/N 315-049930, and the
Modem Block Installation Instructions,
P/N 315-099356.
1.
Mount LLM-1 in the XLS enclosure. Refer to
LLM-1 installation instructions, P/N 315-093530,
for further information
5.
Modem Ratings
14-18 AWG 10 miles Max.
20 AWG 6 Miles Max.
22 AWG 4 miles Max.
0.8 uf max line to line
14-22 AWG unshielded twisted pair
Port #1
DO
NOT
USE
Port #1
x
x
x
Chassis
Ground
67 8
14 15 16
22 23 24
1 WITH HUB-4
ABB
+
--
AB
--
1
9
A
+
PSC-12
TB4+
-
PSC-12
TB4+
-
A
+
(For use with RS-485 only)
-049099
XLS OR FOR DESIGO CC/
CERBERUS DMS ONLY, IN
A XLS/DESIGO FIRE SAFET
MODULAR/CERBERUS
PRO MODULAR
DO
NOT
USE
DO
NOT
USE
x
The interface type
(Modem or RS-485)
must match on each
COM-2 card. If only
one interface is used
on a COM-2 card, it
must be placed on
Port #1 or Port #3
NCC-WAN OR
DESIGO CC/
CERBERUS DMS WAN
Figure 14
Style 4 Wiring Between HUB-4’s (with RS-485 interface or Modem Block)
Figure 15
Style 7 Wiring Between HUB-4’s (with RS-485 interface)
12345678
910111213141516
17 18 19 20 21 22 23 24
ONE SLOT OF CC-5 #1 WITH HUB-4
INSTALLED
AAAABB BB
++
--++
--
AABB
++
--
1234567 8
910111213141516
17 18 19 20 21 22 23 24
ONE SLOT OF CC-5 #1 WITH HUB-4
INSTALLED
AAAABB BB
++
--++
--
AABB
++
--
PSC-12
TB4+
-
PSC-12
TB4+
-
TB1
TB2
LLM-1
12 34
12 34
AABB
++
--
AABB
++
--
TB1
TB2
LLM-1
12 34
12 34
MODEM OR
OR RS-485
INTERFACE
Port #2
MODEM OR
OR RS-485
INTERFACE
Port #3
MODEM OR
OR RS-485
INTERFACE
Port #4
120 OHM EOL
120 OHM EOL
1.
2.
Positive or negative ground fault detected <5K ohms
on CC-5 1-16
P/N 140-049099
P/N 140-049099
XLS or for Desigo CC/
Cerberus DMS only
in a XLS/Desigo Fire
Safety Modular/Cerberus
PRO Modular
* The LLM-1 inserts
10 ohms between
TB1 and TB2
terminals 2 and 3
(20 ohms total).
*
* The LLM-1 inserts
10 ohms between
TB1 and TB2
terminals 2 and 3 (20
ohms total).
*
5.
For more information, refer to the
RS485 Interface Installation
Instructions, P/N 315-049930
3.
Power limited to NFPA 72 per NEC 760
4.
RS-485 Ratings:
Maximum current: 150mA
Maximum voltage: 8Vp-p
14-18AWG Twisted pair or twisted shielded pair
0.34uF max line to line
200 ohms per pair (LLM-1 not included)
DO
NOT
USE
DO
NOT
USE
RS-485
Interface
Port #1
x
xx
x
The interface type
(Modem or RS-485)
must match on each
COM-2 card. If only
one interface is used
on a COM-2 card, it
must be placed on
Port #1 or Port #3
DO
NOT
USE
Chassis
Ground
Chassis
Ground
NCC-WAN
or Desigo CC/
Cerberus DMS
RS-485
Interface
Port #1
Mount LLM in the XLS enclosure, or for Desi
g
o CC/
Cerberus DMS only, in a XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular enclosure. Refer to
LLM-1 installation instructions, P/N 315-093530, for
further information.