Desigo Control Point device description and % of device capacity that is used by integrated data
points
The model of Desigo Control Point device determines the total number of BACnet objects that can
be integrated.
Default integration level
The default integration level is configured in the Data point integration settings and applies to DXRs
only.
To set the Integration level field for all DXRs in the list to your selected default, click Apply to all.
Note
All data points are integrated for non-DXR BACnet devices, regardless of the integration level.
Integrate button
Starts the integration process. This button is enabled when at least one device is selected.
Note
The integration process stops if the number of data points being integrated exceeds the device
capacity.
Close button
Click to close the data point integration function.
Device selection check box
Select individual check boxes or the Select all check box to select devices for data point integration.
The cursor changes to Not available if the device is not available or not ready for data point
integration.
Device
Description of the device being monitored.
Device state
Indicates the availability of each device for data point integration. See the following Table
Device
state indications
for more detail on each state.
Status
Indicates whether the objects from the device have been integrated to the Desigo Control Point
device for monitoring. See the following Table
Status indications
for more detail on each status.