OPC Interface Specifications Version 5.1 FS20EN Document No.
Siemens Smart Infrastructure FS20EN Fire Panel This workbook describes the objects provided by the Siemens OPC Data Access Server to represent the FS20EN fire control unit Legend ID Object Model Description
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0010 FS20EN Alarm Control Individual entity of control logic for alarm handling.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0020 FS20EN Alarm Control Group The Alarm Control Group is the means for organizing specific alarm controls. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 258-Controls Off 265-Controls On 259-Sounders Off 266-Sounders On X X X X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0030 FS20EN Alert Evac Sounders Evacuation sounders used in the Control domain.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0040 FS20EN Alert Sounders Sounders used in the Control domain.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0050 FS20EN Area Off Fire Controls This switches on or off the Fire Controls programmed in the related Area. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 258-Controls Off 265-Controls On \ \ X X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0060 FS20EN Area Off Rts This switches on or off the Remote Transmissions programmed in the related Area. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 258-Controls Off 265-Controls On \ \ X X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0070 FS20EN Area Off Sounders This switches on or off the Audible Souders programmed in the related Area. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 259-Sounders Off 266-Sounders On \ \ X X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0080 FS20EN BACnet Device BACnet device. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State \ \ \ OPC DA Specifications_V5.1_FS20EN.xlsx \ Page 10 of 56
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0090 FS20EN Bypassable Elem Bypassable elements mostly used in the control domain. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 3-Fault 1-Normal Fault X 7-Active 1-Normal Activated X 0-Disable 1-Enable \ \ X X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0100 Object Model Description FS20EN Digital Input Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 3-Fault 1-Normal Fault X 16-Abnormal 1-Normal Anomaly X 0-Disable 1-Enable \ \
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0110 Object Model Description FS20EN Digital Output Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0120 FS20EN Evac Control Individual entity of the control logic related to evacuation.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0130 FS20EN Evac Sounders Evacuation sounder channel.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0140 FS20EN Extinguishing Zone The Extinguishing Zone handles the raw alarm information related to extinguishing sensors.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0150 FS20EN Fire Control Group The Fire Control Group is the means for organizing the various fire controls. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 0-Disable 1-Enable X 2-Test 14-Normal X X X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0160 FS20EN Fire Detector Logical channels used in the detection domain for fire/smoke detection and technical alarms.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0170 FS20EN Fire Subsystem Zone The Fire Subsystem Zone handles the raw alarm information related to different sensor types.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0180 Object Model Description FS20EN Generic Control The Control represents an individual entity of the control logic. Each Control has a dedicated functionality.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0190 Object Model Description FS20EN Generic Digital Input The Input Channels are exclusively used in the logical domain. Specific sensors handle different information from the detection devices and a logical input is used for technical alarms coming from other systems.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0200 Object Model Description FS20EN Generic Element Generic Configuration Element. This element is a member of the operation tree and is mainly used for the configuration of country-specific operations and view peripherals.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0210 Object Model Description FS20EN Key Depot Configuration Element used for the configuration of country-specific operations and view peripherals.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0220 FS20EN Manual Call Point Logical channels used in the detection domain for fire detection.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0230 FS20EN Manual Zone The Manual Zone handles the raw alarm information coming from manual call point.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0240 FS20EN Multi State Value Panel and Area multistate objects for block commands. Commands on OPC Item Present Value States OPC Item PresentValue OPC Item Mode Result State 2-Block Ack 3-Block Reset 4-Block Silence 5-Block Unsillence 2-Acknowledge X X X X 3-Reset X X X X 4-Silence X X X X 5- Unsilence X X X X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0250 FS20EN Notification Class BACnet notification class. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State \ \ \ OPC DA Specifications_V5.1_FS20EN.xlsx \ Page 27 of 56
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0260 Object Model Description FS20EN Output Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls which in turns activate Outputs or Sounders.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0270 Object Model Description FS20EN Panel An entire FS20 host (panel or terminal) with respect to the process information. In addition, a BACnet Device object is associated so that each host can be addressed as an individual node in the BACnet inter-network.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0280 Object Model Description FS20EN Pmi Visibility The PMI Visibility elements are attached to the PMI Config element which models the local PMI of an FS20 station. The subordinate Visibility elements are mainly used for configuration purposes (manual activation).
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0290 Object Model Description FS20EN Pmi Standby Visibility The PMI Visibility elements are attached to the PMI Config element which models the local PMI of an FS20 station. The subordinate Visibility elements are mainly used for configuration purposes (automatic fallback).
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0300 FS20EN Sounders Sounder output logical channel.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0310 FS20EN Sprinkler Zone The Sprinkler Zone handles the raw alarm information coming from sprinklers.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0320 FS20EN Verification Elem Counter which influences the alarm equipment and remote transmission. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Activated 267-Non Default Mode 0-Disabled Disabled 0-Disable 1-Enable X 13-Auto Release Disable \ X X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20EN-0330 FS20EN XC10 Zone Extinguishing panel control. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled X 267-Non Default Mode 13-Automatic Released Disabled Automatic Release Disable X 0-Disable 1-Enable X 279-Auto Release Disable \ X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20EN-0340 Object Model Description FS20EN Event commands This is not an Object Model but provides the read-only information about the event states. The event related to the point can require the acknowledge, silence/unsilence, and reset commands.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20EN-0350 FS20EN Zone The Zone handles the raw alarm information coming from one or more detectors. Different zones (Automatic, Technical, Gas, Multi, Extinguishing, etc.) can be used depending on purpose.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20EN-0360 FS20EN Area The Area controls the alarm organization and switches the system to manned/unmanned state.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20EN-0370 FS20EN Area Propagation This switches on or off the Sections and Zones programmed in the related Area.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20EN-0380 FS20EN Section The Section can be used to operate a collection of zones in a safe and easy way. It provides the functionality for switching to on, off, fast, and test.
OPC Object Specifications_2 ID Object Model Description FS20EN-0390 FS20EN Binary Hvac The Binary Hvac represents the HVAC control for dampers and smoke extractor. Siemens Smart Infrastructure OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 3-Active Active 7-Active OPC Item PresentValue 0-Inactive Commands on OPC Item Mode States X X OPC DA Specifications_V5.1_FS20EN.
OPC Object Specifications_2 ID Object Model Description FS20EN-0400 FS20EN Hvac Control Group The Hvac Control Group is the means for organizing the various HVAC controls. Siemens Smart Infrastructure OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Active 7-Active OPC Item PresentValue 0-Inactive Commands on OPC Item Mode States X X OPC DA Specifications_V5.1_FS20EN.
OPC Object Specifications_2 ID Object Model Description FS20EN-0410 FS20EN Multistate Value Hvac The Multistate Value Hvac represents the general state of a control in a HVAC zone. Siemens Smart Infrastructure OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Active X 3-Fault 1-Normal Fault X 7-Active 0-Inactive Commands on OPC Item Mode States X OPC DA Specifications_V5.1_FS20EN.
OPC Object Specifications_2 ID Object Model Description FS20EN-0420 FS20EN Sub Binary Hvac The Sub Binary Hvac reppesents the HVAC control for dampers and smoke extractor. Siemens Smart Infrastructure OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 3-Active Active 7-Active OPC Item PresentValue 0-Inactive Commands on OPC Item Mode States X X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_3 Gateway Panel to interface the Cloud system. Commands on OPC Item Mode OPC Item Mode Result State 0-Quiet 1-Normal Normal 16-Abnormal 1-Normal Abnormal 1-Enable OPC Item PresentValue 0-Disable States OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_3 Commands on OPC Item Mode OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Active 16-Abnormal 1-Normal Abnormal 7 - Normal 0 - None Normal 7 - Normal 4 - Reset To reset 5 - Ack to fault 0 - None Fault 1-Enable OPC Item PresentValue 0-Disable States 4-Reset The Zone of control for the Extinguishing Sector.
Siemens Smart Infrastructure OPC Object Specifications_3 Object Model Description FS20EN-0450 FS20EN Evac Control Group The Control group of the Evacuation part.
Siemens Smart Infrastructure OPC Object Specifications_3 309-Activate Voice Clear X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 0-Quiet 1-Normal Normal X 267-Non Default Mode 0-Disabled Disabled 267-Non Default Mode 2-Test Test X 302-Activate Voice Evac Fire 1-Normal Active X 303-Activate Voice Evac Alert 1-Normal Active X X 304-Activate Voice Tes
Siemens Smart Infrastructure OPC Object Specifications_3 309-Activate Voice Clear X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 0-Quiet 1-Normal Normal X 267-Non Default Mode 0-Disabled Disabled 267-Non Default Mode 2-Test Test X 302-Activate Voice Evac Fire 1-Normal Active X 303-Activate Voice Evac Alert 1-Normal Active X X 304-Activate Voice Test Escalation 1-Normal Active X X X 307-Activate Voice Schoolbell 1-Normal Active X
OPC Object Specifications_3 FS20EN Extinguishing Control The Control of Extinguishing part. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 2-Test Test 14-Normal FS20EN-0480 2-Test Description 1-Enable Object Model 0-Disable ID Siemens Smart Infrastructure X X OPC DA Specifications_V5.1_FS20EN.
OPC Object Specifications_3 FS20EN Extinguishing Control Group The Control Group of the Extinguishing part. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 2-Test Test 14-Normal FS20EN-0490 2-Test Description 1-Enable Object Model 0-Disable ID Siemens Smart Infrastructure X X OPC DA Specifications_V5.1_FS20EN.
OPC Object Specifications_3 Description FS20EN-0500 FS20EN Extinguishing Digital Output Digital Output dedicated to Extinguishing. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Activated 3-Fault 1-Normal Fault 276-Deactivate Object Model 269-Activate ID Siemens Smart Infrastructure OPC DA Specifications_V5.1_FS20EN.
OPC Object Specifications_3 Description FS20EN-0510 FS20EN LineElem Line Element for field devices connection. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 1-Enable Object Model 0-Disable ID Siemens Smart Infrastructure X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infrastructure OPC Object Specifications_3 ID Object Model FS20EN-0520 FS20EN Sub Control Extinguishing The Zone of control for the Extinguishing Sector. Sector Description Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 7-Active 1-Normal Active 16-Abnormal 1-Normal Abnormal \ \ \ \ \ OPC DA Specifications_V5.1_FS20EN.xlsx \ \ Page 54 of 56
OPC Object Specifications_3 ID Object Model Description FS20EN-0530 FS20EN Line Elem Full Control Bypassable elements mostly used in the control domain. Siemens Smart Infrastructure OPC Item PresentValue OPC Item Mode Result State 0-Disable 0-Quiet 1-Normal Normal X 267-Non Default Mode 0-Disabled Disabled 1-Enable Commands on OPC Item Mode States \ \ X OPC DA Specifications_V5.1_FS20EN.
Siemens Smart Infratructure Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd 2021 Technical specifications and availability subject to change without notice.