Commissioning Instructions

8
Siemens Industry, Inc.
A6V11668992
Restricted
2019-03-12
Using Saturation Level in ABT Site and ABT Inside
Title 24 Fault Detection for VAV and FPB Templates
For compliance with Title 24, an FDD configured template must be used.
FDD templates are located on StdApps under Apogee > Desigo_ABT >
CustomApplications > FaultDetection.
VAV and FPB templates include Saturation level parameters by default. To find and edit
them in ABT Site, go to the Default values task and locate them under Supply air VAV.
They can be edited here before the application is loaded into the controller:
If a controller was already loaded, and these values need to be edited, they can be
changed online using ABT Inside:
1 Go Online with the device.
2 Navigate to Room segment - HVAC
3 Click the three dots next to Supply air VAV.