Commissioning Instructions
19
Siemens Industry, Inc.
A6V11668992
Building Technologies
Restricted
2019-03-12
Configure Central Function for Supply Air VAV Saturation
Evaluation
1. Choose the Central HVAC Function.
2. Choose Supply chain for air.
3. Click the drop down and change None to Supply chain air 11.
4. Choose Supply air VAV saturation evaluation.
5. Click the drop down and change the setting from None to Active.