Commissioning Instructions
13
Siemens Industry, Inc.
A6V11668992
Restricted
2019-03-12
Excluding VAV Terminal from Saturation Calculation
When the Enable Saturation Calculation parameter is set to false, the VAV box is not
included in the Duct Pressure Reset calculation, but it still remains part of the group. The
following example shows how to exclude a box while online in the controller. It can also be
done by changing the same setting in the Default values area in ABT Site.
1 Go Online with the device.
2 Navigate to Room segment - HVAC
3 Click the three dots next to Supply air VAV.
4 Change Enable saturation calculation to “No”.
5 Click OK.