8 The NumVavSuStrtn (Number of supply air VAV air volume flow starved) parameter
may be added to Additional parameters (or may be already exposed). Note that this
object does not need to be pulled out from Show/Hide Parameters; it will be visible /
shown while online even if not selected here.
9 If necessary, select the Avail on AS option for the parameters. (Note that doing this will
increase network traffic.)
10 Click OK.
11 Close the application.
12 Add the VAV Automation Stations to the Building Hierarchy.
If any changes are made to the application configuration (for example, changes
to the I/O) the application must be unlocked with a custom application number.
However, simply changing or adding default values (such as changing StrtnLvl)
does not require a change in the application template number.