Configuring VAV Terminal with Default Values
(Optional)
Although this configuration example is the suggested way of setting up Duct
Static Pressure Reset, it is not the only correct method. There are other ways to
achieve the same result, for example by using the VavSu11 AF (instead of
VavSu12) and Central Functions. VavSu11 uses an external air flow controller /
actuator.
Furthermore, job requirements might necessitate changes in this configuration.
This example is meant to be used as a guideline and not an all-use case.
Note, in your application these object parameters should already be exposed if you are
using standard VAV / FPB templates. Adding them again here will not alter the application
but you do not need to add objects or parameters if they are already exposed.
Skip this section as appropriate.
1 Choose the Configuration component, then choose the Application selection task
2 . Open the VAV application template and choose the Default values task.
3 Choose the Show/hide parameters button.
4 Expand the selections to see the parameters under %RSegm%'HVAC'VavSu