Basic Documentation

Table Of Contents
Disclaimer: These are sample drawings and sequences. Designers are responsible for
finalizing the content for their particular projects.
4. Real time ‘live’ Graphic Programs with auto refresh
5. System Name and Geographic Navigation methods
6. Parameter changes of all adjustable object properties
7. Setpoint Adjustments
8. Viewing Alarms and Events
9. Operators’ Usage
10. Hyperlinks
11. On line help menus
B. BACNET:
1. The BAS server and Operator Workstations shall meet the BACnet device profile of an
Advanced Workstation Server (B-AWS) and Operator Workstation (B-OWS) and shall
support the following BACnet BIBBs:
a. Data Sharing
1) Data Sharing-Read Property-Initiate, Execute (DS-RP-A,B)
2) Data Sharing-Read Property Multiple-Initiate, Execute (DS-RPM-A,B)
3) Data Sharing-Write Property-Initiate, Execute (DS-WP-A,B)
4) Data Sharing-Write Property Multiple-Initiate (DS-WPM-A)
5) Data Sharing-COV-Initiate (DS-COV-A)
b. Scheduling
1) Scheduling-Initiate (SCHED-A)
c. Trending
1) Trending-Viewing and Modifying Trends-Initiate (T-VMT-A)
2) Trending-Automated Trend Retrieval-Initiate (T-ATR-A)
d. Network Management
1) Network Management-Connection Establishment-Initiate (NM-CE-A)
e. Alarming
1) Alarm and Event-Notification-Initiate (AE-N-A)
2) Alarm and Event-ACK-Initiate (AE-ACK-A)
3) Alarm and Event –Alarm Summary-Initiate (AE-ASUM-A)
4) Alarm and Event –Enrollment Summary-Initiate (AE-ESUM-A)
5) Alarm and Event –Information-Initiate (AE-INFO-A)
f. Device Management
1) Device Management-Dynamic Device Binding- Initiate, Execute (DM-
DDB-A, B)
2) Device Management-Dynamic Object Binding- Initiate, Execute (DM-
DOB-A,B)
3) Device Management-Device Communication Control- Initiate (DM-DCC-
A)
4) Device Management-Private Transfer- Initiate, Execute (DM-PT-A,B)
5) Device Management-Text Message-Execute (DM-TM-B)
6) Device Management-Time Synchronization- Initiate (DM-TS-A)
7) Device Management-UTC Time Synchronization- Initiate (DM-UTC-A)
8) Device Management-Reinitialize Device- Initiate (DM-RD-A)
9) Device Management-Backup and Restore- Initiate (DM-BR-A)
10) Device Management-List Manipulation- Initiate, Execute (DM-LM-A,B)
11) Device Management-Object Creation and Deletion- Initiate (DM-OCD-A)
2. The BAS Server and Workstations shall support the following Data Link Layers:
a. BACnet IP Annex J
b. BACnet IP Annex J Foreign Device