User Manual
System Security
Installation/Commissioning
2
16 | 27
A6V11917731_en_b_41
2.2.2 Port Settings
To communicate with in a Novigo/Cerberus PACE system, a PACE PC must be
used, with the PACE-Design software activated.
The computer connected to the Novigo/Cerberus PACE system must use a
standard remote maintenance tool.
The following remote maintenance tools with remote control can be used:
● RDP
● VNC
● FastViewer
With a connection between the computer with remote maintenance tool and a
Novigo/Cerberus PACE system, all the communications must be forwarded
through to the following ports:
RDP Port Settings
Port
Direction
Protocol
Destination Address
Comment
3389
input and output
TCP
IP address Ethernet port
PACE PC
Communication RDP to
PACE PC
VNC Port Settings
Port
Direction
Protocol
Destination Address
Comment
5800
input and output
TCP
IP address Ethernet port
PACE PC
Communication VCN to
PACE PC
5900
input and output
TCP
IP address Ethernet port
PACE PC
Communication VCN to
PACE PC
5900
input and output
UDP
IP address Ethernet port
PACE PC
Communication VCN to
PACE PC
FastViewer Port Settings
Port
Direction
Protocol
Destination Address
Comment
80
input and output
TCP
IP address Ethernet port
PACE PC
Communication
FastViewer too PACE PC
443
input and output
TCP
IP address Ethernet port
PACE PC
Communication
FastViewer too PACE PC
5000
input and output
TCP
IP address Ethernet port
PACE PC
Communication
FastViewer too PACE PC
If other remote maintenance tools are used, only the used ports can be released.
With a connection between an MMS or a tablet designer and a Novigo/Cerberus
PACE system, the communication must be forwarded through to the following
ports:
Communication between MMS/Tablet Designer and the PACE System
Port
Direction
Protocol
Destination Address
Comment
Port configuration
based on the API
configuration in
PACE-Design
Input and output
TCP
Any
Communication
through PACE API