User Manual
Operating Reference
Alarms
3
A6V10415471_en_a_40 223 | 352
Fast/Investigative Treatment Workflow
Acknowledgment Model Scenario Event Status
ACK and Reset required ● Event handling started (and at least
one event-handling command sent)
● Event source back to Quiet
Unprocessed
Waiting for
condition
Ready to be closed
Closed
● Event handling not started yet (no
event-handling command sent yet)
● Event source back to Quiet
Unprocessed
Ready to be closed
Closed
No Reset (ACK only required) ● Event handling started (and at least
one event-handling command sent)
or not started yet (no command
sent yet)
● Event source back to Quiet
Unprocessed
Waiting for
condition
Closed
No ACK, No Reset ● Event handling started (and at least
one event-handling command sent)
or not started yet (no command
sent yet)
● Event source back to Quiet
Waiting for
condition
Closed
Optional ACK, No Reset ● Event handling started (and at least
one event-handling command sent)
or not started yet (no command
sent yet)
● Event source back to Quiet
Unprocessed
Waiting for
condition
Closed
Assisted Treatment (with Mandatory Steps) Workflow
Acknowledgment Model Scenario Event Status
ACK and Reset required ● Event handling started (and at least
one event-handling command sent)
● Event source back to Quiet
Unprocessed
Waiting for
condition
Ready to be reset
Waiting for
condition (due to
mandatory steps)
Ready to be closed
Closed
● Event handling not started yet (and
no event-handling command sent
yet)
● Event source back to Quiet
Unprocessed
Ready to be reset
Waiting for
condition (due to
mandatory steps)
Ready to be closed
Closed
No Reset (ACK only required) ● Event handling started (and at least
one event-handling command sent)
● Event source back to Quiet
Unprocessed
Waiting for
condition
Waiting for
condition (due to
mandatory steps)
Ready to be closed
Closed