User Manual

Operating Reference
Alarms
3
A6V10415471_en_a_40 223 | 352
Fast/Investigative Treatment Workflow
Acknowledgment Model Scenario Event Status
ACK and Reset required Event handling started (and at least
one event-handling command sent)
Event source back to Quiet
Unprocessed
Waiting for
condition
Ready to be closed
Closed
Event handling not started yet (no
event-handling command sent yet)
Event source back to Quiet
Unprocessed
Ready to be closed
Closed
No Reset (ACK only required) Event handling started (and at least
one event-handling command sent)
or not started yet (no command
sent yet)
Event source back to Quiet
Unprocessed
Waiting for
condition
Closed
No ACK, No Reset Event handling started (and at least
one event-handling command sent)
or not started yet (no command
sent yet)
Event source back to Quiet
Waiting for
condition
Closed
Optional ACK, No Reset Event handling started (and at least
one event-handling command sent)
or not started yet (no command
sent yet)
Event source back to Quiet
Unprocessed
Waiting for
condition
Closed
Assisted Treatment (with Mandatory Steps) Workflow
Acknowledgment Model Scenario Event Status
ACK and Reset required Event handling started (and at least
one event-handling command sent)
Event source back to Quiet
Unprocessed
Waiting for
condition
Ready to be reset
Waiting for
condition (due to
mandatory steps)
Ready to be closed
Closed
Event handling not started yet (and
no event-handling command sent
yet)
Event source back to Quiet
Unprocessed
Ready to be reset
Waiting for
condition (due to
mandatory steps)
Ready to be closed
Closed
No Reset (ACK only required) Event handling started (and at least
one event-handling command sent)
Event source back to Quiet
Unprocessed
Waiting for
condition
Waiting for
condition (due to
mandatory steps)
Ready to be closed
Closed