Alarms
3
218 | 352 A6V10415471_en_a_40
intervention text may or may not be available to you. For instructions, see Get
More Information About the Event [ 42].
(start investigative treatment) or (start assisted treatment). For
instructions, see Start Investigative Treatment [ 44] and Start Assisted
Treatment [ 47].
You cannot resize
Information
column.
Event Status
Describes the status of the event [ 222]. For example: Unprocessed, Ready
to be reset, and so on.
Source Status
Describes the status of the event source: Active (event source is in an off-normal
condition) or Quiet (event source is back to normal).
Date/Time
Date and time when the event occurred. Typically, event time displays with
resolution hh:mm:ss. However, in special cases, it will display with resolution
hh:mm:ss:ms.
ID
Unique number that identifies the event. This number has an upper limit. The
numbering restarts when this limit is reached.
In Process by
Indicates which user is processing an event. Depending on the type of Desigo CC
client you are working on, one of the following may display:
Installed client: [computer name]/[full name of the logged-on
user]
If the computer/user data was not specified in the configuration,
[localhost]+[user’s short name] displays instead.
Web client or web app client: Web Client/[Operator’s full name].
Furthermore, for recurrences [ 225] of the same event, this column displays the
entire list of computer/users that are processing that event. Depending on the
Client Profile, recurring events may not be available.
Suggested action
Describes the next action [ 222] the operator should take for handling the event.
Category
Describes the event category.
The events that occur in the building control system are grouped into categories,
which are color-coded by severity. The specific category names and colors
employed are dependent on the event schema.