Basic Documentation
9/11
Building Automation BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_06 Building Automation BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_06
CPS 03-22-2017
1.5 Client supported object types
Object type
Supported
Can be created
dynamically
Can be deleted
dynamically
Analog Input
ý
¨
¨
Analog Output
ý
¨
¨
Analog Value
ý
¨
¨
Binary Input
ý
¨
¨
Binary Output
ý
¨
¨
Binary Value
ý
¨
¨
Calendar
ý
ý
ý
Command
ý
ý
ý
Device
ý
¨
¨
Event Enrollment
ý
ý
ý
File
ý
¨
¨
Group
ý
¨
¨
Loop
ý
¨
¨
Multi-State Input
ý
¨
¨
Multi-State Output
ý
¨
¨
Notification Class
ý
ý
ý
Program
ý
¨
¨
Schedule
ý
ý
ý
Averaging
ý
¨
¨
Multi-State Value
ý
¨
¨
Trend Log
ý
ý
ý
Life-Safety-Point
ý
¨
¨
Life-Safety-Zone
ý
¨
¨
Accumulator
ý
¨
¨
Pulse-Converter
ý
¨
¨
Event Log
ý
¨
¨
Global Group
ý
¨
¨
Trend Log Multiple
ý
ý
ý
Load Control
ý
¨
¨
Structured-View
ý
¨
¨
Access Door
¨
¨
¨
Access Credential
¨
¨
¨
Access Point
¨
¨
¨
Access Rights
¨
¨
¨
Access User
¨
¨
¨
Access Zone
¨
¨
¨
Credential Data Input
¨
¨
¨
Network Security
ý
¨
¨
Bitstring Value
ý
¨
¨
Characterstring Value
ý
¨
¨