Desigo™ CC MP 3.
Contents 1 Desigo CC Workstation ..............................................................................
1 Desigo CC Workstation Date Vendor name Product name Product model number BACnet protocol version Application software version Firmware revision 1.1 : March 22, 2017 : Siemens Building Technologies (Vendor ID 7) : Desigo CC Workstation : 3.0 : 13 : 3.0 : n/a Product description Desigo CC from Siemens is an integration platform for managing facility systems and enterprise applications.
1.
Alarm and event management Scheduling Historical/Deprecated BIBBs ý Alarm and Event – Alarm Summary-A ý ý Alarm and Event – Enrollment Summary-A AE-ESUM-A Alarm and Event – Information-A AE-INFO-A ¨ ¨ ý ý ý ¨ ¨ Scheduling – Internal-B SCHED-I-B Scheduling – External-B SCHED-E-B Scheduling – View Modify-A SCHED-VM-A Scheduling – Advanced View Modify-A SCHED-AVM-A Scheduling – Weekly Schedule-A SCHED-WS-A Scheduling – Weekly Schedule Internal-B SCHED-WS-I-B Scheduling – Readable-B SCHED-
Device management Network management ý ¨ ý ¨ ý ¨ ý ¨ ¨ ¨ ý ý ý ¨ ¨ ¨ ý ý ý ý Device Management – TimeSynchronization-A DM-TS-A Device Management – TimeSynchronization-B DM-TS-B Device Management – UTCTimeSynchronization-A DM-UTC-A Device Management – UTCTimeSynchronization-B DM-UTC-B Device Management – ReinitializeDevice-A DM-RD-A Device Management – ReinitializeDevice-B DM-RD-B Device Management – Backup and Restore-A DM-BR-A Device Management – Backup and Restore-B DM-BR-B Device Manag
1.4 Standard object types supported Only the device object is supported.
Properties Auto_Slave_Discovery Slave_Address_Binding Last_Restart_Reason Time_Of_Device_Restart Restart_Notification_Recipients UTC_Time_Synchronization_Recipients Time_Synchronization_Interval Align_Intervals Interval_Offset Serial_Number Property_List Profile_Name monitor modify ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ý ¨ ¨ ¨ ¨ ¨ ý ¨ ¨ ¨ ¨ ¨ ¨ 8/11 Building Automation CPS DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS) CM110665en_06 03-22-2017
1.
Object type Date Pattern Value Date Value Datetime Pattern Value Datetime Value Integer Value Large Analog Value Octetstring Value Positive Integer Value Time Pattern Value Time Value Notification Forwarder Alert Enrollment Channel Lighting Output Supported ý ý ý ý ý ý ý ý ý ý ý ý ¨ ¨ Can be created dynamically Can be deleted dynamically ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ 10/11 Building Automation CPS DESIGO™ BACnet Protocol Implementation Conformance Statement (PICS) CM110665e
1.6 ý ý Segmentation capability Able to transmit segmented messages Window size 32 Able to receive segmented messages 32 1.7 ý ý ý ¨ ¨ ¨ ¨ ¨ ¨ ¨ ¨ Window size Data Link Layer options BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7) ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) MS/TP master (Clause 9), baud rate(s) MS/TP slave (Clause 9), baud rate(s) Point-To-Point, EIA 232 (Clause 10), baud rate(s) : Max.