OPC Interface Specifications Version 5.0 SiPass Document No.
Siemens Smart Infrastructure SiPass This workbook describes the objects provided by the Siemens OPC Data Access Server to represent the SIPass Access Control system Legend ID Object Model Description
OPC Object Specifications ID Object Model Description SIPASS-0010 AC AntipassbackArea Individual entity of control logic for APB area.
OPC Object Specifications ID Object Model Description SIPASS-0020 AC Device AC Device is the main hardware access component States Siemens Smart Infrastructure Commands on OPC Item State 71-UnitCommunicationLost 72-UnitCommunicationBack 73-UnitReset 74-UnitTamperActive 75-UnitTamperInactive OPC DA Specifications_V5.0_SiPass.
Siemens Smart Infrastructure OPC Object Specifications ID Object Model Description SIPASS-0030 AC Doorset The Door object is the logical representation of the single/dual reader door States Commands on OPC Item Reader 2 State (if not configured, always 0-NotConfigured ) 19-Lock (Latch State) 20-Unlock (Latch State) 32-Block (Block State) X X Door Frame State Latch State Block State Passback state 48-DoorClosed 112/69-OutputEnabled/Locked 109-DoorUnblocked 64-InputEnabled 68-FaultClear
OPC Object Specifications ID Object Model Description SIPASS-0040 AC Input Physical Input States State Commands on OPC Item 3-Enable 2-Disable X 46-PointNormal 63-InputDisabled Siemens Smart Infrastructure X 107-PointAlarm X 58-InputTamper X 117-InputUnsealed X 118-InputSealed X OPC DA Specifications_V5.0_SiPass.
OPC Object Specifications ID Object Model Description SIPASS-0050 AC Intrusion Area Specific area configured as intrusion area Siemens Smart Infrastructure Commands on OPC Item State 37-Arm X 83-Armed 84-Disarmed X 85-IntrusionAreaAlarm X 87-AreaArmingFailed 39-Disarm X X OPC DA Specifications_V5.0_SiPass.
OPC Object Specifications ID Object Model Description SIPASS-0060 AC Output Physical Output States State Commands on OPC Item 8-Secure 9-Unsecure X 69-Locked 70-Unlocked Siemens Smart Infrastructure X OPC DA Specifications_V5.0_SiPass.
OPC Object Specifications ID Object Model Description SIPASS-0070 AC Module AC Module represents different types of boards (DRI,SRI,IPM,OPM…) States Siemens Smart Infrastructure Commands on OPC Item State 3-Online 2-CommunicationLost OPC DA Specifications_V5.0_SiPass.
OPC Object Specifications ID Object Model Description SIPASS-0080 Sipass Server AC Module is the main hardware access component States Siemens Smart Infrastructure Commands on OPC Item State Login State 3-Connected 201-Login Successful 1-Disconnected 2-Trying 4-Lost 5-Failure 0-Not Logged In 400/404-Login Error 408-Timeout Request 500-LoginFailed 900-UnauthorizedAccess 902-SipassServiceNotAvailable 903/204-InternalServerError 905-InvalidTimeIntervalOfConnection 908-SessionExpired 909-InputNot
OPC Object Specifications ID Object Model Description SIPASS-0090 AC Flag Logic point. States Commands on OPC Item 46 - Activate State 105-FlagTrue 106-FlagFalse Siemens Smart Infrastructure 47 - Deactivate X X OPC DA Specifications_V5.0_SiPass.
OPC Object Specifications ID Object Model Description SIPASS-00100 AC External Device AC External Device is the main hardware access component for external subsystems connected to SiPass (i.e. SALTO) States Siemens Smart Infrastructure Commands on OPC Item State 129-Online 130-Offline OPC DA Specifications_V5.0_SiPass.
OPC Object Specifications ID Object Model Description SIPASS-00110 AC External Point AC External point is the logic representation for points connected through the external device States Siemens Smart Infrastructure Commands on OPC Item State 136 - Door Tamper 137 - Door Online 138 - Door Offline OPC DA Specifications_V5.0_SiPass.
Siemens Smart Infrastructure Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd 2021 Technical specifications and availability subject to change without notice.