OPC Interface Specifications Version 4.0 FS20EN Document No.
Siemens Building Technologies FS20EN Fire Panel This workbook describes the objects provided by the Siemens OPC Data Access Server to represent the FS20EN fire control unit Legend ID Object Model Description
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0010 Object Model Description FS20EN Alarm Control Individual entity of control logic for alarm handling.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0020 Object Model Description FS20EN Alarm Control Group The Alarm Control Group is the means for organizing specific alarm controls. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 258-Controls Off 265-Controls On 259-Sounders Off 266-Sounders On X X X X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0030 Object Model Description FS20EN Alert Evac Sounders Evacuation sounders used in the Control domain.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0040 Object Model Description FS20EN Alert Sounders Sounders used in the Control domain.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0050 Object Model Description FS20EN Area Off Fire Controls This switches on or off the Fire Controls programmed in the related Area. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 258-Controls Off 265-Controls On \ \ X X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0060 Object Model Description FS20EN Area Off Rts This switches on or off the Remote Transmissions programmed in the related Area. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 258-Controls Off 265-Controls On \ \ X X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0070 Object Model Description FS20EN Area Off Sounders This switches on or off the Audible Souders programmed in the related Area. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 259-Sounders Off 266-Sounders On \ \ X X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0080 Object Model Description FS20EN BACnet Device BACnet device. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State \ \ \ OPC DA Specifications_V4.0_FS20EN.xlsx \ Page 10 of 55
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0090 Object Model Description FS20EN Bypassable Elem Bypassable elements mostly used in the control domain. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 3-Fault 1-Normal Fault X 7-Active 1-Normal Activated X 0-Disable 1-Enable \ \ X X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0100 Object Model Description FS20EN Digital Input Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 3-Fault 1-Normal Fault X 16-Abnormal 1-Normal Anomaly X 0-Disable 1-Enable \ \
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0110 Object Model Description FS20EN Digital Output Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0120 Object Model Description FS20EN Evac Control Individual entity of the control logic related to evacuation.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0130 Object Model Description FS20EN Evac Sounders Evacuation sounder channel.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0140 Object Model Description FS20EN Extinguishing Zone The Extinguishing Zone handles the raw alarm information related to extinguishing sensors.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0150 Object Model Description FS20EN Fire Control Group The Fire Control Group is the means for organizing the various fire controls. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 0-Disable 1-Enable X 2-Test 14-Normal X X X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0160 Object Model Description FS20EN Fire Detector Logical channels used in the detection domain for fire/smoke detection and technical alarms.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0170 Object Model Description FS20EN Fire Subsystem Zone The Fire Subsystem Zone handles the raw alarm information related to different sensor types.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0180 Object Model Description FS20EN Generic Control The Control represents an individual entity of the control logic. Each Control has a dedicated functionality.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0190 Object Model Description FS20EN Generic Digital Input The Input Channels are exclusively used in the logical domain. Specific sensors handle different information from the detection devices and a logical input is used for technical alarms coming from other systems.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0200 Object Model Description FS20EN Generic Element Generic Configuration Element. This element is a member of the operation tree and is mainly used for the configuration of country-specific operations and view peripherals.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0210 Object Model Description FS20EN Key Depot Configuration Element used for the configuration of country-specific operations and view peripherals.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0220 Object Model Description FS20EN Manual Call Point Logical channels used in the detection domain for fire detection.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0230 Object Model Description FS20EN Manual Zone The Manual Zone handles the raw alarm information coming from manual call point.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0240 Object Model Description FS20EN Multi State Value Panel and Area multistate objects for block commands. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 2-Block Ack 3-Block Reset 4-Block Silence 5-Block Unsillence 2-Acknowledge X X X X 3-Reset X X X X 4-Silence X X X X 5- Unsilence X X X X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0250 Object Model Description FS20EN Notification Class BACnet notification class. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State \ \ \ OPC DA Specifications_V4.0_FS20EN.xlsx \ Page 27 of 55
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0260 Object Model Description FS20EN Output Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls which in turns activate Outputs or Sounders.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0270 Object Model Description FS20EN Panel An entire FS20 host (panel or terminal) with respect to the process information. In addition, a BACnet Device object is associated so that each host can be addressed as an individual node in the BACnet inter-network.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0280 Object Model Description FS20EN Pmi Visibility The PMI Visibility elements are attached to the PMI Config element which models the local PMI of an FS20 station. The subordinate Visibility elements are mainly used for configuration purposes (manual activation).
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0290 Object Model Description FS20EN Pmi Standby Visibility The PMI Visibility elements are attached to the PMI Config element which models the local PMI of an FS20 station. The subordinate Visibility elements are mainly used for configuration purposes (automatic fallback).
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0300 Object Model Description FS20EN Sounders Sounder output logical channel.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0310 Object Model Description FS20EN Sprinkler Zone The Sprinkler Zone handles the raw alarm information coming from sprinklers.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0320 Object Model Description FS20EN Verification Elem Counter which influences the alarm equipment and remote transmission. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Activated 267-Non Default Mode 0-Disabled Disabled 0-Disable 1-Enable X 13-Auto Release Disable \ X X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0330 Object Model Description FS20EN XC10 Zone Extinguishing panel control. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled X 267-Non Default Mode 13-Automatic Released Disabled Automatic Release Disable X 0-Disable 1-Enable X 279-Auto Release Disable \ X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_1 ID FS20EN-0340 Object Model Description FS20EN Event commands This is not an Object Model but provides the read-only information about the event states. The event related to the point can require the acknowledge, silence/unsilence, and reset commands.
Siemens Building Technologies OPC Object Specifications_2 Description FS20EN Zone The Zone handles the raw alarm information coming from one or more detectors. Different zones (Automatic, Technical, Gas, Multi, Extinguishing, etc.) can be used depending on purpose.
Siemens Building Technologies OPC Object Specifications_2 ID Object Model Description FS20EN-0360 FS20EN Area The Area controls the alarm organization and switches the system to manned/unmanned state.
Siemens Building Technologies OPC Object Specifications_2 ID Object Model Description FS20EN-0370 FS20EN Area Propagation This switches on or off the Sections and Zones programmed in the related Area.
Siemens Building Technologies OPC Object Specifications_2 Description FS20EN Section The Section can be used to operate a collection of zones in a safe and easy way. It provides the functionality for switching to on, off, fast, and test.
OPC Object Specifications_2 ID Object Model Description FS20EN-0390 FS20EN Binary Hvac The Binary Hvac represents the HVAC control for dampers and smoke extractor. Siemens Building Technologies OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 3-Active Active 7-Active OPC Item PresentValue 0-Inactive Commands on OPC Item Mode States X X OPC DA Specifications_V4.0_FS20EN.
OPC Object Specifications_2 ID Object Model Description FS20EN-0400 FS20EN Hvac Control Group The Hvac Control Group is the means for organizing the various HVAC controls. Siemens Building Technologies OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Active 7-Active OPC Item PresentValue 0-Inactive Commands on OPC Item Mode States X X OPC DA Specifications_V4.0_FS20EN.
OPC Object Specifications_2 ID Object Model Description FS20EN-0410 FS20EN Multistate Value Hvac The Multistate Value Hvac represents the general state of a control in a HVAC zone. Siemens Building Technologies OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Active X 3-Fault 1-Normal Fault X 7-Active 0-Inactive Commands on OPC Item Mode States X OPC DA Specifications_V4.0_FS20EN.
OPC Object Specifications_2 ID Object Model Description FS20EN-0420 FS20EN Sub Binary Hvac The Sub Binary Hvac reppesents the HVAC control for dampers and smoke extractor. Siemens Building Technologies OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 3-Active Active 7-Active OPC Item PresentValue 0-Inactive Commands on OPC Item Mode States X X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_3 Gateway Panel to interface the Cloud system. Commands on OPC Item Mode OPC Item Mode Result State 0-Quiet 1-Normal Normal 16-Abnormal 1-Normal Abnormal 1-Enable OPC Item PresentValue 0-Disable States OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_3 Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Active 16-Abnormal 1-Normal Abnormal 7 - Normal 0 - None Normal 7 - Normal 4 - Reset To reset 5 - Ack to fault 0 - None Fault 1-Enable OPC Item Mode 0-Disable OPC Item PresentValue 4-Reset Commands on OPC Item Mode States 2-Ack to Fault The Zone of control for the Extinguishing Sector.
Siemens Building Technologies OPC Object Specifications_3 Object Model Description FS20EN-0423 FS20EN Evac Control Group The Control group of the Evacuation part.
Siemens Building Technologies OPC Object Specifications_3 309-Activate Voice Clear X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 0-Quiet 1-Normal Normal X 267-Non Default Mode 0-Disabled Disabled 267-Non Default Mode 2-Test Test X 302-Activate Voice Evac Fire 1-Normal Active X 303-Activate Voice Evac Alert 1-Normal Active X X 304-Activate Voice Te
Siemens Building Technologies OPC Object Specifications_3 309-Activate Voice Clear X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 0-Quiet 1-Normal Normal X 267-Non Default Mode 0-Disabled Disabled 267-Non Default Mode 2-Test Test X 302-Activate Voice Evac Fire 1-Normal Active X 303-Activate Voice Evac Alert 1-Normal Active X X 304-Activate Voice Test Escalation 1-Normal Active X X X 307-Activate Voice Schoolbell 1-Normal Active
OPC Object Specifications_3 FS20EN Extinguishing Control The Control of Extinguishing part. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 2-Test Test 14-Normal FS20EN-0426 2-Test Description 1-Enable Object Model 0-Disable ID Siemens Building Technologies X X OPC DA Specifications_V4.0_FS20EN.
OPC Object Specifications_3 The Control Group of the Extinguishing part. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 2-Test Test 14-Normal FS20EN-0427 2-Test Description 1-Enable Object Model FS20EN Extinguishing Control Group 0-Disable ID Siemens Building Technologies X X OPC DA Specifications_V4.0_FS20EN.
OPC Object Specifications_3 Description FS20EN-0428 Digital Output dedicated to Extinguishing. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Activated 3-Fault 1-Normal Fault 276-Deactivate Object Model FS20EN Extinguishing Digital Output 269-Activate ID Siemens Building Technologies OPC DA Specifications_V4.0_FS20EN.
OPC Object Specifications_3 Object Model Description FS20EN-0429 FS20EN LineElem The Zone of control for the Extinguishing Sector. Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Disable States 0-Quiet 1-Normal Normal X 267-Non Default Mode 0-Disabled Disabled 1-Enable ID Siemens Building Technologies X OPC DA Specifications_V4.0_FS20EN.
Siemens Building Technologies OPC Object Specifications_3 Commands on OPC Item Mode OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 0-Disabled Disabled 7-Active 1-Normal Active 16-Abnormal 1-Normal Abnormal 1-Enable OPC Item PresentValue 0-Disable States OPC DA Specifications_V4.0_FS20EN.xlsx 14-Normal The Zone of control for the Extinguishing Sector.
Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd 2019 Technical specifications and availability subject to change without notice.