3 System Security Guidelines
The NK823x Ethernet port is a BACnet gateway that can integrate legacy fire and
intrusion detection systems over serial connections and provide Cerberus DMS
with a BACnet/IP connectivity over local and remote networks.
NK823x units can also support onboard I/O lines and local DF8000 I/O modules.
NOTICE
The NK823x firmware specific for Desigo CC/Cerberus DMS must be downloaded
to the NK823x unit before using it with Cerberus DMS. For instructions, in the
Cerberus DMS online help, see Checking and Updating NK823x Firmware and
Kernel.
Fig. 1: NK823x Ethernet Port
NOTICE
BACnet/IP unprotected protocol on TCP/IP
The communication between Cerberus DMS and NK823x is based on the
BACnet/IP, which is an unprotected protocol on TCP/IP. This requires that the
connection between Cerberus DMS and the NK823x Ethernet port must be
protected from attacks and unauthorized access.
Fig. 2: Unprotected Connection Between Cerberus DMS and NK823x
LAN ( Ethernet TCP / IP )
Server / Client Client
AlgoRex
CS11 STT11/20 DF8000
Sintony
SI410
NK823x CC is BACnet GW
Upstream Protocol
BACnet/IP
FS20