Data Sheet for Product

Regulated Facility Solution Set Matrix
© Siemens 2012-2021. All rights reserved. Document ID: A6V11273358_enUS_c March 2021
Regulated Facility
Firmware
Desigo CC Software
Datamate Advanced Software
Network
Data Integrity
Data integrity for the APOGEE Automation System is verified through system validation. This ensures that the APOGEE Automation System meets an organization’s user requirements and any applicable regulatory requirements. Siemens has developed standard specifications and system verification
templates to aid an organization in the validation of the APOGEE Automation System. Templates based on current industry practices save time and money on the project. To ensure the APOGEE Automation System is maintained in a “Validated state throughout its lifetime, a comprehensive service
offering can be established.
Protection of Records
11.10 (b), 11.10 (c)
Password security and physical security must be enabled at the
field panels. It is recommended that a binary door monitoring
switch be added to each field panel used to collect information,
and that local access capability be disabled.
It is recommended that power be sourced from an
uninterrupted power supply (UPS), and the UPS is sourced
from emergency power grid. This practice eliminates loss of
data due to power blackouts, brownouts, surges, or dips.
Desigo CC software retains complete copies of system records in both human readable and
electronic form, available for inspection, review and copying.
It is recommended that power be sourced from an uninterrupted power supply (UPS) and the
UPS is sourced from emergency power grid. This practice eliminates loss of data due to
power blackouts, brownouts, surges, or dips.
Install robust server designs with built-in redundancy to protect data stored on the server hard
disk. Execute SOPs that regularly back up critical electronic records.
Access to the system is controlled using Windows integrated security. Users do not have to
manage a unique set of usernames and passwords. Using an individual’s domain account
name and password, the system can detect user access and will grant them access to only
those functions they are authorized to use. This access control is used to determine what
functions a user can use, what they can see, print, or otherwise have access to.
Datamate Advanced software retains complete copies of system records in both
human readable and electronic form, available for inspection, review and copying.
Access to the system is controlled using Windows integrated security. It is
recommended that access capability be limited to selected individuals and their
supervisor.
Desigo CC server is synchronized with Network
Time.
All components with time functions in the
APOGEE Automation System are automatically
synchronized to the system server daily.
Redundancy of network components is
recommended to ensure protection of records.
Trend
It is necessary to collect Trend Data from field panels as often
as possible to mitigate and/or significantly reduce possible loss
of data stored in panel RAM. This design consideration must
be considered in detail in specifications and validated.
The ability to change Trend Definitions is restricted by Desigo CC Access and Privileges. It
is recommended that access capability be limited to selected individuals and their supervisor.
The ability to change Trend Definitions is restricted by Datamate Advanced Access
and Privileges. It is recommended that access capability be limited to selected
individuals and their supervisor.
The ability to change Alarm parameters in Point Definitions is restricted by Access
and Privileges. It is recommended that access capability be to selected individuals
and their supervisor.
Records of changes made using Datamate Advanced software must be printed
periodically for secure, long-term storage. Records can be printed to paper or saved
as PDF files.
Not Applicable
Alarms
Alarm configuration is part of the Point Definition database.
System alarm records are automatically managed by the Desigo CC application. The ability
to change Alarm parameters in Point Definitions is restricted by access and privileges. It is
recommended that access capability be limited to selected individuals and their supervisor.
System Activity
At the field panel, local system access is not recommended.
All system changes should be made using Desigo CC software
to ensure a complete audit trail of all changes.
Desigo CC software will acquire records as they are created, lock them down in a secure
database, provide the ability to retain them for a user definable and/or indefinite time and
provide modern reporting functionality to visualize the data.
Point Definitions
The ability to change Point Definitions is restricted by ALN
Access and Privileges. It is recommended that access
capability be disabled.
The ability to change Point Definitions is restricted by Desigo CC Access and Privileges. It is
recommended that access capability be limited to selected individuals and their supervisor.
The ability to change Point Definitions is restricted by Datamate Advanced Access
and Privileges. It is recommended that access capability be limited to selected
individuals and their supervisor.
Not Applicable
PPCL
At the field panel, PPCL programs are stored in the EEPROM
memory and protected from data loss by battery within the
field panel. The ability to change PPCL programs is restricted
by ALN Access and Privileges. It is recommended that access
capability be disabled.
The ability to change PPCL is restricted by Access and Privileges. It is recommended that
access capability be limited to selected individuals and their supervisor. It is recommended
that PPCL modifications be accomplished through Desigo CC to ensure a complete audit trail
of changes.
The ability to change PPCL is restricted by Datamate Advanced Access and
Privileges. It is recommended that access capability be limited to selected
individuals and their supervisor.
Records of changes made using Datamate Advanced software must be printed
periodically for secure, long-term storage. Records can be printed to paper or saved
as PDF files.
Audit Trails
11.10 (e)
BACnet (Firmware) is an open communication protocol that
supports changes from devices external to the system. These
types of changes do not leave an audit trail. The BACnet
network must be secured procedurally to prevent users at
external devices from making changes.
Desigo CC software provides an automatic audit trail of any changes made to, Point
Definitions and other critical objects designated for enhanced audit trails. The Desigo CC
application captures and documents changes to APOGEE Automation System operations.
Desigo CC software will acquire records as they are created, lock them down in a secure
database, provide the ability to retain them for a user definable and/or indefinite time and
provide modern reporting functionality.
Desigo CC software manages system activity and operator transaction records.
Datamate Advanced software provides an audit trail of any changes made to PPCL,
Point Definitions and other critical point modifications executed via Datamate
Advanced.
Records of changes made using Datamate Advanced software must be printed
periodically for secure, long-term storage. Records can be printed to paper or saved
as PDF files.
Not Applicable
System Security
11.10 (d), 11.10 (f), 11.10 (g),
11.10 (h), 11.10 (j), 11.10 (k),
11.30
Password security and physical security must be enabled at the
field panels. It is recommended that a binary door monitoring
switch be added to each field panel used to collect information.
This demonstrates compliance with US FDA regulations, and
that the ALN system access is limited to a single individual
and their supervisor.
Systems that use Desigo CC flex client and click-once client must incorporate additional
security authentication measures, encryption mechanisms, firewall, and/or SSL (secure socket
layer) type technologies into building automation design.
Access to the system is controlled using Windows integrated security. Users do not have to
manage a unique set of usernames and passwords. Using domain accounts, the system can
detect an individual’s user access level and will grant them access to only those functions
they are authorized to use.
Access to the system is controlled using Windows integrated security. Users do not
have to manage a unique set of usernames and passwords. Using each individual’s
Windows account name and password, the system can detect user access and can
grant them access to only those functions they are authorized to use. This access
control is used to determine what functions a user can use, what they can view, print,
or otherwise have access.
Access rights to system records, reports, report
templates, and client applications are all
controlled using Windows integrated security.
Windows integrated security is designed and
configured properly to limit system access
through an SOP.
Electronic Signatures
11.50(a)(b), 11.70, 11.100,
11.200,11.300
Not Applicable
Not Applicable
Not Applicable
PDF based report output option can be combined
with Adobe’s or a third-party signature handler
and\ or a document management system.
Establish Procedures
11.10(j)
The customer must develop their own Standard Operating Procedures (SOPs) for the proper use and operation of the BAS. Siemens recommends that the following SOPs be developed for a customer site: System Operating Procedures, Backup Procedures, Change Control/Upgrade Procedures,
Hardware Maintenance Procedures, Calibration Procedures, Software Maintenance Procedures, System Security Procedures, Training Procedures, Electronic Records/Data Management Procedures, Incident Management Procedures and Disaster Recovery Procedures.
Control Documents
11.10(k)
The customer must have the required documentation available and protected. Revision and change control procedures should be in place for all the required documentation. The list of the required documentation includes, but is not limited to: User Requirements, Functional Specification, Configuration
Specifications, Operations and Maintenance Manuals, Training Records, Calibration Records, System Drawings, Completed Protocol Documents, System Acceptance and Sign-off and Maintenance Records.