Desigo™ Control Point BACnet/IP Web Interface PXG3.W100-1, PXG3.W200-1 Web-based, graphical operation of BACnet automation stations using Desigo touch panels and devices with an HTML 5.0 web browser.
Use Topology The web interfaces PXG3.W100-1 and PXG3.W200-1 are the central points of access to operate the automation level and room automation of a BACnet System. The central point of access permits simultaneous operation on various operator units and supports ● Connection of Desigo touch panels PXM30-1, PXM40-1 and PXM50-1 ● Access via devices using a standard web browser with HTML5.
Example graphic for a primary plant.
Service button Button Press Description S Short Physical identification on the network (Ethernet) As per description Do the following to delete the device: 1. 2. 3. Switch off the device. Switch on the device. Wait until all LEDs turn on and then off and then press the S button. 4. Keep the S button pressed until the green RUN LED starts to flash and then release. 5. Wait until the device has fully started – unconfigured (RUN LED on, SVC LED flashes).
Type summary Type Stock number for ordering Designation PXG3.W100-1 S55842-Z117 BACnet/IP web interface with standard functionality PXG3.W200-1 S55842-Z118 BACnet/IP web interface with extended functionality Product documentation Type of document Document no. Data sheet for touch panels 7", PXM30-1, PXM30.E A6V11554092 Data sheet for touch panels 10.1" and 15.6", PXM40-1, PXM40.E, PXM50-1, PXM50.
Maintenance The devices are maintenance-free. Firmware upgrade Firmware upgrades are loaded with ABT Site (at startup, user initiated). Use either the Ethernet or USB interface. Repair The devices cannot be repaired. The entire unit must be replaced. Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose.
Connections Screw terminals, plug-in Cu-wire or Cu-strand with wire end sleeve 1 x 0.6 mm∅ to 2.5mm2 (22 to 14 AWG) or 2 x 0.6 mm∅ to 1.0 mm2 (22 to 18 AWG) Cu-strand without wire end sleeve 1 x 0.6 mm∅ to 2.5 mm2 (22 to 14 AWG) or 2 x 0.6 mm∅ to 1.5 mm2 (22 to 16 AWG) Stripping length 6...7.5 mm (0.24...0.29 in) Screwdriver Slot screws Screwdriver, size 1 with shaft ø ≤ 4.5 mm Max. tightening torque 0.6 Nm (0.
Standards, directives and approvals Product standard EN 60730-1 Automatic electronic controls for household and similar use Product family standard EN 50491-x General requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS) Electromagnetic compatibility (EMC) For residential, commercial, and industrial environments EU conformity (CE) See CE declaration CM1T9270xx 1) EAC compliance Eurasian compliance RCM conformity See RCM declaration CM1T922
294z04_02 Connection diagrams 1, 2 2 x RJ45 interface for Ethernet 3 24 V ~, Operating voltage AC/DC 24 V , USB USB tool interface Dimensions All dimensions in mm (in.) 17.7 (0.7") 4 (0.16") 7.5 (0.3") 43.6 (1.72") 70 (2.76") 90 (3.54") 9294M01_03 162 (6.38") 45 (1.77") 3 (0.19") 35.3 (1.39") 54 (2.13") 109 (4.29") 54 (2.13") 90 (3.54") 5.14 (0.2") Trademarks Oracle and Java are trademarks or registered trademarks of Oracle America, Inc. Siemens Industry, Inc.
Issued by Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000 10 Siemens Industry, Inc. Building Technologies Document ID A6V11554090_enUS Edition 2018-10-26 © Siemens Industry, Inc., 2018 Technical specifications and availability subject to change without notice.