OPC Interface Specifications Version 4.0 XLS Document No.
Siemens Building Technologies XLS Fire Panel This workbook describes the objects provided by the Siemens OPC Data Access Server to represent the XLS fire control unit Legend ID Object Model Description
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0010 XLS Audio Zone Submodule Modules providing amplifier circuits. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 3-Fault 1-Normal 267-Non Default Mode 12-Disabled 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X X Fault X X X X Disabled X X X OPC DA Specifications_V4.0_XLS.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0020 XLS Ckt Device Output circuit driven by system behavior. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 3-Fault 1-Normal 267-Non Default Mode 12-Disabled 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X X Fault X X X X Disabled X X X X OPC DA Specifications_V4.0_XLS.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0030 XLS Control Submodule Module to send live pages to specific speaker. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 5 of 53
Siemens Building Technologies OPC Object Specifications ID XLS-0040 Object Model Description XLS Conventional Module Module that allows conventional smoke detectors to be used with the FireFinder XLS system. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 3-Fault 1-Normal 267-Non Default Mode 12-Disabled 4 - Enable 5 - Disable Normal X X Fault X X Disabled X X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 6 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0050 XLS Conventional Zone Component Component that allows conventional smoke detectors to be used with the FireFinder XLS system. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 3-Fault 1-Normal 267-Non Default Mode 12-Disabled 4 - Enable 5 - Disable Normal X X Fault X X Disabled X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 7 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0060 XLS Conventional Zone Device Device capable of supporting Siemens compatible conventional smoke detectors. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 1-Normal 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable Normal X X Alarm X X 1-Normal Fault X X 12-Disabled Disabled X X States \ \ Commands on OPC Item Convention
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0070 XLS DAC Module Digita audio card to control voice-system modules. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 9 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0080 XLS DLC Device loop card. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 10 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0090 XLS Default Device Input/output devices used for speaker, telephone line, municipal tie, leased line, and so on. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 1-Normal 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable Normal X X Alarm X X 1-Normal Fault X X 12-Disabled Disabled X X States \ \ Commands on OPC Item LED.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0090 cont. States Commands on OPC Item Switch1.Present Value OPC Item Switch1.PresentValue Result State 512-Quiet 514-Alarm 4 - Enable 5 - Disable Normal X X Alarm X X 515-Fault Fault X X 267-Non Default Mode Disabled X X 268-Trouble Bypass Enabled X X States \ \ Commands on OPC Item Relay1.Present Value OPC Item Relay1.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0100 XLS Default Module Input/output control modules used for strobe, horn and notification appliance. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 3-Fault 1-Normal 267-Non Default Mode 12-Disabled 4 - Enable 5 - Disable Normal X X Fault X X Disabled X X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 13 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0110 XLS Default Submodule Submodules for input/output supervision, especially for voice and audio applications. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 14 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0120 XLS Detector Component Smoke and fire components. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 1-Normal 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable Normal X X Alarm X X 1-Normal Fault X X 12-Disabled Disabled X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 15 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0130 XLS Detector Device Smoke and fire detectors. Part I States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable Normal X X 1-Normal Alarm X X 1-Normal Fault X X 12-Disabled Disabled X X States \ \ Commands on OPC Item AudBaseAlert.Present Value OPC Item AudBaseAlert.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0130 States Part I cont. Commands on OPC Item AudBaseEvac.Present Value OPC Item AudBaseEvac.PresentValue Result State 512-Quiet 514-Alarm 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X X Alarm X X X X 515-Fault Fault X X X X 267-Non Default Mode Disabled X X X X 268-Trouble Bypass Enabled X X X X States Commands on OPC Item AudBaseOther.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0130 XLS Detector Device Smoke and fire detectors. Part II States Commands on OPC Item Ambient.Present Value OPC Item Ambient.PresentValue Result State 512-Quiet 4 - Enable 5 - Disable Normal X X 514-Alarm Alarm X X 515-Fault Fault X X 267-Non Default Mode Disabled X X 268-Trouble Bypass Enabled X X States \ \ Commands on OPC Item CO.Present Value OPC Item CO.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0130 Part II cont. States Commands on OPC Item MultiCrit.Present Value OPC Item MultiCrit.PresentValue Result State 512-Quiet 514-Alarm 4 - Enable 5 - Disable Normal X X Alarm X X 515-Fault Fault X X 267-Non Default Mode Disabled X X 268-Trouble Bypass Enabled X X States \ \ Commands on OPC Item Neural.Present Value OPC Item Neural.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0130 XLS Detector Device Smoke and fire detectors. Part III States Commands on OPC Item Relay1.Present Value OPC Item Relay1.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0130 Part III cont. States Commands on OPC Item SmokePhoto.Present Value OPC Item SmokePhoto.PresentValue Result State 512-Quiet 514-Alarm 4 - Enable 5 - Disable Normal X X Alarm X X 515-Fault Fault X X 267-Non Default Mode Disabled X X 268-Trouble Bypass Enabled X X States \ \ Commands on OPC Item Thermal.Present Value OPC Item Thermal.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0140 XLS DLC Device loop card. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 22 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0150 XLS HCP Output Device Intelligent control point, capable of switching on and supporting a notification appliance circuit, telephone, or speaker zone that is remotely located near a detector loop.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0160 XLS HTRI Device Addressable interface module. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 1-Normal 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable Normal X X Alarm X X 1-Normal Fault X X 12-Disabled Disabled X X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 24 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0170 XLS HTRI Relay Device Addressable interface module with relay output. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X X 1-Normal Alarm X X X X 1-Normal Fault X X X X 12-Disabled Disabled X X X X OPC DA Specifications_V4.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0180 XLS ILED Device ILED device States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X X 1-Normal Alarm X X X X 1-Normal Fault X X X X 12-Disabled Disabled X X X OPC DA Specifications_V4.0_XLS.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0190 XLS LED Component LED Component. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable Normal X X 1-Normal Alarm X X 1-Normal Fault X X 12-Disabled Disabled X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 27 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0200 XLS LED Device Indicator LED. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 1-Normal 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable Normal X X Alarm X X 1-Normal Fault X X 12-Disabled Disabled X States \ \ Commands on OPC Item LED.Present Value OPC Item LED.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0210 XLS Manual Station Device Manual pull station. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 1-Normal 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable Normal X X Alarm X X 1-Normal Fault X X 12-Disabled Disabled X X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 29 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0220 XLS Network Interface Module Module that provides solid-state relay outputs at locations that are remote from a node's central enclosure States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 30 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0230 XLS OCM-16 Module Module that provides solid-state relay outputs at locations that are remote from a node's central enclosure States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State \ \ 0-Quiet 1-Normal Normal X X 3-Fault 1-Normal Fault X X 267-Non Default Mode 12-Disabled Disabled X X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 31 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0240 XLS Panel XLS panel node. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0 - Quiet 1-Normal 2 - Alarm 1-Normal 3 - Fault 267-Non Default Mode 4 - Connect 5 - Disconnect Normal X X Not Reachable X X 1-Normal Security X X 12-Disabled Disconnected X X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 32 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0250 XLS PMI Module Control panel module. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault 267-Non Default Mode 12-Disabled Disabled \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 33 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0260 XLS Port Device Parallel and serial ports. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 34 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0270 XLS Power Module Primary and extender power supply. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 1-Normal 267-Non Default Mode 1-Normal 4 - Enable 5 - Disable Normal X X Fault X X Security X X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 35 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0280 XLS Power Supply Submodule Primary and extender power supply submodules. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 3-Fault 1-Normal 6 - Activate 7 - Deactivate Normal X X Fault X X OPC DA Specifications_V4.0_XLS.xlsx \ \ Page 36 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0290 XLS Printer Module Remote printer module which processes one parallel port and two serials ports. States Commands on OPC Item Mode OPC Item Mode OPC Item PresentValue Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 37 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0300 XLS Pseudo Device Non-existing device used for logic function purposes only. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault 22-Supervisory 1-Normal Supervisory 267-Non Default Mode 1-Normal Security 268-Non Default Mode 12-Disabled Disabled \ OPC DA Specifications_V4.0_XLS.xlsx \
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0310 XLS Pseudo Module Non-existing module used for logic function purposes only. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 1-Normal Disabled \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 39 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0320 XLS Relay Component Programmable relay component. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 1-Normal 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X X Alarm X X X X 1-Normal Fault X X X X 1-Normal Disabled X X X OPC DA Specifications_V4.0_XLS.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0330 XLS Relay Output Device Programmable relay element. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal 2-Alarm 1-Normal 3-Fault 267-Non Default Mode 4 - Enable 5 - Disable 6 - Activate 7 - Deactivate Normal X X X X Alarm X X X X 1-Normal Fault X X X X 1-Normal Disabled X X X X States Commands on OPC Item Relay1.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0340 XLS SCM Non-existing module used for logic function purposes only. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 3-Fault 1-Normal Fault 267-Non Default Mode 1-Normal Disabled \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 42 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0350 XLS Switch Component Component for supervision which makes the element addressable to a FireFinder XLS node.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0360 XLS Switch Input Device Module for input supervision which makes the element addressable to a FireFinder XLS node.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0370 XLS Switch Input Device No License Module for input supervision which makes the element addressable to a FireFinder XLS node.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0380 XLS Unidentified Unidentified event object. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault 22-Supervisory 1-Normal Supervisory 267-Non Default Mode 1-Normal Security 268-Non Default Mode 12-Disabled Disabled \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 46 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0390 XLS VESDA Component VESDA components used for smoke detection with continuous air sampling. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault 22-Supervisory 1-Normal Supervisory 267-Non Default Mode 1-Normal Disabled \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 47 of 53
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0400 XLS VESDA Device VESDA devices used for smoke detection with continuous air sampling.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0400 Part I cont. States Commands on OPC Item Alert.Present Value OPC Item Alert.PresentValue Result State 512-Quiet 514-Alarm 4 - Enable 5 - Disable Normal X X Alarm X X 515-Fault Fault X X 267-Non Default Mode Disabled X X 268-Trouble Bypass Enabled X X States \ \ Commands on OPC Item Fire1.Present Value OPC Item Fire1.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0400 Part I cont. States Commands on OPC Item Fire1.Present Value OPC Item Fire2.PresentValue Result State 512-Quiet 514-Alarm 4 - Enable 5 - Disable Normal X X Alarm X X 515-Fault Fault X X 267-Non Default Mode Disabled X X 268-Trouble Bypass Enabled X X States \ \ Commands on OPC Item Fire1.Present Value OPC Item Scan.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0400 XLS VESDA Device VESDA devices used for smoke detection with continuous air sampling. Part II States Commands on OPC Item Fire2.Present Value OPC Item Fire2.PresentValue Result State 512-Quiet 4 - Enable 5 - Disable Normal X X 514-Alarm Alarm X X 515-Fault Fault X X 267-Non Default Mode Disabled X X 268-Trouble Bypass Enabled X X States \ \ Commands on OPC Item Scan.
Siemens Building Technologies OPC Object Specifications ID Object Model Description XLS-0410 XLS VPM VESDA peripheral module. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 3-Fault 1-Normal Fault \ OPC DA Specifications_V4.0_XLS.xlsx \ \ \ Page 52 of 53
Siemens Building Technologies Siemens Industry Inc. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000 © Siemens Industry Inc. 2019 Technical specifications and availability subject to change without notice.