Data Sheet for Product
9
Siemens Specification Texts A6V11547800_en_a_30
Building Technologies 2018-10-01
Specified product: Siemens / Desigo CC Compact or similar
Navigation
Graphic displays must include the ability to dynamically zoom and switch among various layers
with different information. For efficient navigation in clients and smart devices, the system must
provide thumbnail based navigation for the operator (click once) when the Simplified User
Interface is being used.
Specified product: Siemens / Desigo CC Compact or similar
In graphics commanding
The system must offer graphic objects which can be used to command or control the system. At
a minimum, sliders, buttons, text boxes, dropdown lists and radio buttons must be included
Specified product: Siemens / Desigo CC Compact or similar
Visualize the quality state in the plant graphics
A violation of energy efficiency limit values for measured values of primary plants (e.g.
centralized air handling, energy generation) must also be displayed in the plant graphic directly
on the application components or function. The parameters for monitoring, evaluating and
forming the quality state can be set directly in the plant graphic based on read and write access
rights.
Specified products: Siemens / Desigo CC Compact or similar
Pictures
Graphic symbols and standards
Plant graphics must meet the ergonomic needs of the operator. The displayed graphic symbols
must correspond to the generally valid standard for HVAC symbols (DIN EN 62424 (VDE0810-
24)) and ASHRAE guidelines. The symbols must be supported as 2 and 3 dimensional graphics.
The ability is required to create colored floor displays and system diagrams for each mechanical
facility including AHU, chilled water plants, hot water boiler systems, and room operator units.
Associated print outs of standardized plant images must be added to the bid.
Specified product: Siemens / Desigo CC Compact or similar
Object-oriented graphics
The building automation and control system must offer dynamic, high-resolution graphics. The
graphics must be object-oriented. Each symbol must be able to display several states in the
same, consistent format.
At the same time, several views must be able to be open concurrently, and all views must be
updated dynamically.
Specified products: Siemens / Desigo CC Compact or similar
Continuous update and display
Measured values, setpoints, user settings, and alarms must be displayed immediately and
continuously. State changes must be indicated via symbol, e.g. using animation or changing the
color, in general, however, graphic presentation, or text.
Specified products: Siemens / Desigo CC Compact or similar
1.1.4 Scheduler programs
General
Management via central scheduler programs
Operate all scheduler programs online from the management level to achieve consistent,
transparent operation of all integrated systems and subsystems.
Specified products: Siemens / Desigo CC Compact or similar