Data Sheet for Product

8
Siemens Specification Texts A6V11547800_en_a_30
Building Technologies 2018-10-01
1.1.2 User profiles
User privileges
The building automation and control system must allow engineers to define, change, or delete
predefined configurations as per their user privileges.
Specified products: Siemens / Desigo CC Compact or similar
Simplified Operator Interface (Lite UI)
Note: Lite UI is now available for BA_EN only, so please tailor this part according to your system
deployment.
The building automation and control system must allow operators to efficiently maneuver the
controlled equipment. The navigation within system applications and components is achieved by
thumbnail icons and via grouping of functionalities.
A simplified operator interface is assigned to system users. The interface can be applied to more
than one user. The following functionalities must be by default available for the system Operator:
· Managing of System Events (alarm management)
· Operate the installation via graphic application
· Navigate via thumbnails
· Time Scheduler
· Trend Viewer
· Log Viewer
· Report Application
· Document Viewer
· Remote Notifications
The operating interface shall include a workflow based documentation that helps the operator to
manipulate the management station. The document shall be provided in PDF format.
Specified products: Siemens / Desigo CC Compact or similar
1.1.3 Graphics
General
Operating interface to CAD system
The user interface must allow users access to various system schematics and floor plans using graphical
depictions, menu selections, and data point assignments. The graphics software must also permit the
import of CAD symbols (DWG, DXF format) or scanned images for use in the system.
Specified product: Siemens / Desigo CC Compact or similar
Operating messages
Operating messages must be able to be displayed and evaluated on the management level.
Graphics must be able to display data point states that are overwritten by a local priority switch.
This on data points that were developed to supplying by local override.
Specified product: Siemens / Desigo CC Compact or similar
Full graphics mode
A fully graphics-based management level with ergonomic and freely scalable images must be
available. The system must be developed to operating, monitor, optimize, and log all connected
subsystems in real time.
Specified product: Siemens / Desigo CC Compact or similar
Graphics generation
Based on their user rights, operators must be able to add, delete, and edit system graphics and
state texts for digital data points from the standard user interface without external or special
tools.