Data Sheet for Product

15
Siemens Specification Texts A6V11547800_en_a_30
Building Technologies 2018-10-01
Intermediate storage of history data
Trend data are collected in the automation station and transferred to the management level after
a specific time has expired or specific number of data has been recorded. Trend data may not be
lost if the management station is unavailable temporarily.
Specified products: Siemens / Desigo CC Compact or similar
Trend comparison
The system must offer a time adjusted trend view to run analysis of changed conditions at
various times.
Specified product: Siemens / Desigo CC Compact or similar
1.2 Connectivity
1.2.1 General
Interfaces
The building automation and control system must be scalable to ensure long-term operation and provide all
standard interfaces commonly available on today's market.
Specified product: Siemens / Desigo System or similar
Integrate Third-party devices via OPC
The OPC Foundation must test and certify the system, which must be able to integrate and edit
OPC data, and yet supply real time OPC data as an OPC server. System processing must
include alarming, trend, scheduler, reporting, and be able to communicate with other devices.
The system must support the OPC specification:
ยท OPC DA (Data Access)
Specified product: Siemens / Desigo CC Compact or similar
Integrate via Modbus TCP
The management station must support communication to Modbus TCP/IP devices and sub
systems directly from the management station.
Specified product: Siemens / Desigo CC Compact or similar
Integrate Simatic Devices
The management station must support native integration of Simatic Devices (S7
300/400/1200/1500)
Specified product: Siemens / Desigo CC Compact or similar
1.2.2 Standard BACnet / AMEV
DIN EN ISO 16484-5 / AMEV
AMEV (Management station) AMEV Profile MBE-A and MBE-B
The management stations must meet AMEV profiles MBE-A and MBE-B as per AMEV guideline
"BACnet 2011" V1.1.
Specified products: Siemens / Desigo CC Compact or similar
B-AWS (management station)
The required management stations match the BACnet profile B-AWS (advanced management
station) as per BTL Listing and ANSI / ASHRE 135 guidelines. They must also support BACnet
data points and BACnet personal safety security zone functionality. The BACnet protocol
revision must be at least 13.
Specified product: Siemens / Desigo CC Compact or similar