Data Sheet for Product
14
Siemens Specification Texts A6V11547800_en_a_30
Building Technologies 2018-10-01
· List of all current data points in an override state
· List of all disabled data points
· List of alarm strategy definitions
· Overall data point report
· Data point trend data listing
· Initial value report
· User activity report
· Event history report
Specified product: Siemens / Desigo CC Compact or similar
Customized report templates
The system must permit generated, specific reports as well as individual report templates that
may include graphics and trend views.
Specified product: Siemens / Desigo CC Compact or similar
1.1.9 Remote operation
Operating options
Via web browser
User must be able to remotely operate and engineer plants regardless of location. Of course, this
openness cannot place the plant security at risk. The client must run on a browser as a full trust
client application.
Specified product: Siemens / Desigo CC Compact or similar
Desktop Installed client
User must be able to remotely operate and engineer plants regardless of location. Of course, this
openness cannot place the plant security at risk. The client must operate as a fully installed
software installation, locked with a desktop and prevents in this manner software from being
minimized or hidden by other applications.
Specified product: Siemens / Desigo CC Compact or similar
Via App
User must be able to remotely monitor and control the connected system via a smartphone or
tablet App for Android and iOS. The app must allow to view and manage the events. A secure
network connection between the System and the App must be established. The App must be
intuitive and easy to operate without the need to reconfigure the system.
Specified product: Siemens / Desigo CC Compact or similar
1.1.10 Trend data
Analyses
Simultaneous, multiple trends
Multiple trend views must be possible simultaneously to provide a comprehensive plant
overview. Standard plants from small to medium complexity (as in this project) require a
simultaneous display of up to 10 trend curves on the current page view to assess the plants.
Multiple trend curves must thus be recorded at the same time.
Specified products: Siemens / Desigo CC Compact or similar
Record history data, trend
Vital data points and setpoints must be saved for each building services plant. The polling time is
oriented to the signal type, i.e. analog values are recorded cyclically while digital or multistate
values are recorded by event.
Specified products: Siemens / Desigo CC Compact or similar