Data Sheet for Product
13
Siemens Specification Texts A6V11547800_en_a_30
Building Technologies 2018-10-01
1.1.7 Event management
Event routing and sorting
Event messages can be displayed on each workstation in a table application and must include
the following information: Name, value, event time and date, state, priority, acknowledge
information, and alarm counter. The system must also be able to send out an acoustic message
appropriate to the event category.
Specified product: Siemens / Desigo CC Compact or similar
Event message
Event messages can be displayed on each workstation in a table application and must include
the following information on each event: Name, value, event time and date, state, priority,
acknowledge information, and alarm counter. Each event must also be able to send out an
acoustic message appropriate to the event category.
Specified product: Siemens / Desigo CC Compact or similar
Event acknowledgement
The user can acknowledge each event directly from the list, suppress the acoustic notification,
print or delete it. The interface must also have an option to deleted active, acknowledged events
until it is reset to the normal state. The user must be able to navigate to information associated
with a data point.
Specified product: Siemens / Desigo CC Compact or similar
Event treatment
The system must provide multiple alarm-handling options. These are to be configured in
alignment the standard operating procedures.
Fast Treatment
The user must be able to acknowledge each event directly from the event list, suppress the
acoustic notification, print or delete it. The interface must also have an option to deleted active,
acknowledged events until it is reset to the normal state. The user must also be able to navigate
to information associated with a data point.
Investigative Treatment
From the event list, operators shall have the ability to quickly focus on the source of the event,
and all information (recent history, schedules, and so on.) related to the event source.
Specified product: Siemens / Desigo CC Compact or similar
1.1.8 Report generation
Reports
Report generation
The system must allow generation of customized or predefined reports, to provide important
plant data at any time. The reports must be printable and exportable as a PDF file. The data
must be able to be edited in other programs (Microsoft Excel or Microsoft Access) for further
analysis.
Specified product: Siemens / Desigo CC Compact or similar
Standard report templates
Template to generate detailed reports at little effort. At least three different report templates must
be available.
· Reports to record alarm and fault states
· Reports to record logbook entries
· Reports to record plant and control cabinet states.