Data Sheet for Product
12
Siemens Specification Texts A6V11547800_en_a_30
Building Technologies 2018-10-01
Specified product: Siemens / Desigo CC Compact or similar
Alarm routing
Media independent formats
Current alarms may need to be routed independent of media at certain times to a central service
(printer, email, SMS, pagers, and mobile apps). The number of data points that can be
configured for remote messaging of alarm conditions. The number of remote devices that may
receive system messages may not be limited. The system must support the sending of
encrypted e-mails.
Specified product: Siemens / Desigo CC Compact or similar
Alarm message escalation list
The system must be able to send messages to individuals, or a group of people, and various
messages to different remote devices by message priority. It must also be able to send to an
escalation list, so that a message is sent to a second device if there is no response from the first
device after a configurable time.
Specified product: Siemens / Desigo CC Compact or similar
Acknowledgment
Operator units for acknowledgement
All alarms (alarms and faults, errors) must be acknowledgeable after issue of individual rights
from all connected workstations. For tracking reason, a time stamp and assignment (based on
user account) is required.
This includes:
· Local acknowledgement (control cabinet, automation station)
· Management level
· Remote operating equipment
Specified products: Siemens / Desigo CC Compact or similar
Alarm display
Color display
Incoming alarms must be colored for quick and easy interpretation. Both order and state as well
as alarm priority must be recognizable. The alarm window must be displayed as per operator
needs.
Specified products: Siemens / Desigo CC Compact or similar
Alarm message content
The message texts must contain all information necessary to allocate and resolve the error. This
includes at least the following attributes:
· Clear text.
· Control cabinet name
· Plant name
· Priority
· Timestamp
· Time.
· Status (acknowledged, unacknowledged).
Specified products: Siemens / Desigo CC Compact or similar
Filter alarms
The building automation and control system must offer alarm filtering. Filtering must be possible
by alarm lists or priorities. Alarms are displayed in popup windows.
Specified products: Siemens / Desigo CC Compact or similar