User Guide

System Security Guidelines
Operation/Maintenance
3
16 | 26
A6V11979523_en_b
A
Requirements
TCP/IP 10BaseT (100BaseT or 100BaseT (NK823x only)), 250
Kbit/sec bandwidth required
B
Ports
TCP Ports 20 and 21 (FTP for the configuration download
to NK823x)
TCP Port 22 (SSH Secure Shell)
TCP Port 20500 (if secure configuration and firmware
download is enabled)
TCP Port 4000 for service messages
UDP Port 47808 (hex BAC0) is default for BACnet
connectivity, but is configurable
C
Bandwidth measures
Normal operations:
0.1 Kbit/sec per NK823x + 0.1 Kbit/sec per control unit.
Peaks (firmware and configuration downloads):
64 Kbit/sec (file transfer, around 5 sec) per NK823x
D
Web server
Webserver never enabled for NK823x for Desigo CC.
A
Requirements
Depends on communication characteristics of the control unit.
For example, a serial link at 9600 bps with LAN adapter will
require 1 Kbps.
B
TCP ports
Depends on specific communication characteristics. Typically,
this is configurable in software.
C
Bandwidth measures
Depends on specific communication characteristics.
In case of serial links with LAN adapter, it is
recommended to consider the entire serial baud rate as