OPC Interface Specifications Version 5.1 FS20UL Document No.
Siemens Smart Infrastructure FS20UL Fire Panel This workbook describes the objects provided by the Siemens OPC Data Access Server to represent the FS20UL fire control unit Legend ID Object Model Description
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0010 FS20UL Alarm Control Individual entity of control logic for alarm handling. 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled 267-Non Default Mode 2-Test Test X 7-Active 1-Normal Activated X 3-Fault 1-Normal Fault X X X X X X X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0020 FS20UL Alarm Control Group The Alarm Control Group is the means for organizing specific alarm controls . Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 258-Controls Off 265-Controls On 259-Sounders Off 266-Sounders On States 0-Quiet 1-Normal Normal X X X X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0030 FS20UL Alert Evac Sounders Evacuation sounders used in the Control domain.
Siemens Smart Infrastructure OPC Object Specifications_1 Description FS20UL-0040 FS20UL Alert Sounders Sounders used in the Control domain.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0050 FS20UL Area Off Fire Controls This switches on or off the Fire Controls programmed in the related Area. OPC Item PresentValue OPC Item Mode Result State 258-Controls Off 0-Quiet 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled 265-Controls On Commands on OPC Item Mode States \ \ X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0060 FS20UL Area Off Rts This switches on or off the Remote Transmissions programmed in the related Area. OPC Item PresentValue OPC Item Mode Result State 258-Controls Off 0-Quiet 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled 265-Controls On Commands on OPC Item Mode States \ \ X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0070 FS20UL Area Off Sounders This switches on or off the Audible Souders programmed in the related Area. OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 259-Sounders Off OPC Item PresentValue 266-Sounders On Commands on OPC Item Mode States \ \ X X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0080 FS20UL BACnet Device BACnet device. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State \ \ \ OPC DA Specifications_V5.1_FS20UL.xlsx \ Page 10 of 47
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0090 FS20UL Bypassable Elem Bypassable elements mostly used in the control domain. OPC Item PresentValue OPC Item Mode Result State 0-Disable 0-Quiet 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled 3-Fault 1-Normal Fault X 7-Active 1-Normal Activated X 1-Enable Commands on OPC Item Mode States \ \ X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0100 FS20UL Digital Input Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders. OPC Item PresentValue OPC Item Mode Result State 0-Disable 0-Quiet 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled 3-Fault 1-Normal Fault X 16-Abnormal 1-Normal Anomaly X 1-Enable Commands on OPC Item Mode States \ \
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0110 FS20UL Digital Output Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0120 FS20UL Evac Control Individual entity of the control logic related to evacuation.
Siemens Smart Infrastructure OPC Object Specifications_1 Description FS20UL-0130 FS20UL Evac Sounders Evacuation sounder channel. Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Disable 271-Activate Evac States 0-Quiet 1-Normal Normal X X 268-Trouble Bypass 0-Disabled Disabled 7-Active 1-Normal Activated X 3-Fault 1-Normal Fault X X 16-Abnormal 1-Normal Anomaly X X X 276-Deactivate Object Model 1-Enable ID X X OPC DA Specifications_V5.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0140 FS20UL Extinguishing Zone The Extinguishing Zone handles the raw alarm information related to extinguishing sensors.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0150 FS20UL Fire Control Group The Fire Control Group is the means for organizing the different kinds of fire controls. 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled X X X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0160 FS20UL Fire Detector Logical channels used in the detection domain for fire/smoke detection and technical alarms.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0170 FS20UL Fire Subsystem Zone The Fire Subsystem Zone handles the raw alarm information related to different sensor types.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0180 FS20UL Generic Control Individual entity of the control logic. Each Control has a dedicated functionality.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20UL-0190 Object Model Description FS20UL Generic Digital Input Input Channels exclusively used in the logical domain. Specific sensors handle the different information from the detection devices and a logical input is used for technical alarms coming from other systems.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0200 FS20UL Generic Element Generic Configuration Element. This element is a member of the operation tree and is mainly used for the configuration of country-specific operations and view peripherals.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0210 FS20UL Line P2 Bypassable elements mostly used in the control domain. OPC Item PresentValue OPC Item Mode Result State 0-Disable 0-Quiet 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled 1-Enable Commands on OPC Item Mode States \ \ X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0220 FS20UL Manual Pull Station Logical channels used in the detection domain for fire detection.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0230 FS20UL Manual Zone The Manual Zone handles the raw alarm information coming from manual call point.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0240 FS20UL Multi State Value Panel and Area multistate objects for block commands. Commands on OPC Item PresentValue 2-Block Ack 3-Block Reset 4-Block Silence 5-Block Unsillence States 2-Acknowledge X X X X 3-Reset X X X X 4-Silence X X X X 5-Unsilence X X X X OPC Item PresentValue OPC Item Mode Result State OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0250 FS20UL Notification Class BACnet notification class. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State \ \ \ OPC DA Specifications_V5.1_FS20UL.xlsx \ Page 27 of 47
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0260 FS20UL Output Logical Channels exclusively used in the control domain. Inputs are used to trigger Controls, which in turn activate Outputs or Sounders.
Siemens Smart Infrastructure OPC Object Specifications_1 ID FS20UL-0270 Object Model Description FS20UL Panel An entire FS20 host (panel or terminal) with respect to the process information. In addition, a BACnet Device object is associated so that each host can be addressed as an individual node in the BACnet inter-network.
Siemens Smart Infrastructure OPC Object Specifications_1 Description FS20UL Pmi Visibility The PMI Visibility elements are attached to the PMI Config element which models the local PMI of an FS20 station. The subordinate Visibility elements are mainly used for configuration purposes (manual activation).
Siemens Smart Infrastructure OPC Object Specifications_1 FS20UL-0290 Object Model Description FS20UL Pmi Standby Visibility The PMI Visibility elements are attached to the PMI Config element which models the local PMI of an FS20 station. The subordinate Visibility elements are mainly used for configuration purposes (automatic fallback).
Siemens Smart Infrastructure OPC Object Specifications_1 Description FS20UL-0300 FS20UL Sounders Sounder output logical channel.
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0310 FS20UL Physical Device Device in the hardware domain used in the detection loop. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled \ \ \ OPC DA Specifications_V5.1_FS20UL.xlsx \ Page 33 of 47
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0320 FS20UL Verification Elem Counter which influences the alarm equipment and remote transmission. Commands on OPC Item Mode States OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 7-Active 1-Normal Activated \ \ \ OPC DA Specifications_V5.1_FS20UL.xlsx \ Page 34 of 47
Siemens Smart Infrastructure OPC Object Specifications_1 ID Object Model Description FS20UL-0330 FS20UL Voice Control Group The means for organizing the different kind of voice controls.
Siemens Smart Infrastructure OPC Object Specifications_1 OPC Item Acked Transitions OPC Item Operation Expected OPC Item Silence 7-Normal 0-None 3 - All Silenced 6-Ack to offnormal 1-Silence 0 - Unsilenced X 6-Ack to offnormal 7-Unsilence 3 - All Silenced X 5-Ack to fault 0-None 3 - All Silenced 7-Normal 4-Reset 0 - Unsilenced 7-Normal 4-Reset 3 - All Silenced Commands on OPC Item Silence Command on OPC Item Operation Expected 4-Reset Commands on OPC Item Acked Transitions State
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0350 FS20UL Zone The Zone handles the raw alarm information coming from one or more detectors. Different zones (Automatic, Technical, Gas, Multi, Extinguishing, and so on) can be used depending on purpose.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0360 FS20UL Area The Area controls the alarm organization.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0370 FS20UL Area Propagation This switches on or off the Sections and Zones programmed in the related Area.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0380 FS20UL Section The Section can be used to operate a collection of zones in a safe and easy way. It provides the functionality for switching to on, off, fast, and test.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0390 FS20UL Line MXL Bypassable elements mostly used in the control domain. OPC Item Mode Result State 0-Quiet 1-Normal Normal 268-Trouble Bypass 0-Disabled Disabled 1-Enable OPC Item PresentValue 0-Disable Commands on OPC Item Mode States \ \ X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0400 FS20UL Line Elem Full Control Bypassable elements mostly used in the control domain. OPC Item PresentValue OPC Item Mode Result State 0-Disable 0-Quiet 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled 1-Enable Commands on OPC Item Mode States \ \ X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0410 FS20UL Control Evac Uni The means for organizing the different kind of Evac controls. Result State 0-Disable 0-Quiet 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled 267-Non Default Mode 2-Test Test 14-Normal Mode OPC Item Mode 2-Test OPC Item PresentValue 1-Enable Commands on OPC Item Mode States X X X X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0420 FS20UL Control Group OEO The means for Control Group of OEO functionality. OPC Item PresentValue OPC Item Mode Result State 2-Test 0-Quiet 1-Normal Normal X 267-Non Default Mode 2-Test Test 14-Normal Mode Commands on OPC Item Mode States \ \ X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0430 FS20UL Voice Control The means for organizing the different kind of voice controls.
Siemens Smart Infrastructure OPC Object Specifications_2 ID Object Model Description FS20UL-0440 FS20UL Nac Sounder Device in the hardware domain used for the Sounder NAC. OPC Item PresentValue OPC Item Mode Result State 0-Disable 0-Quiet 1-Normal Normal X 268-Trouble Bypass 0-Disabled Disabled 1-Enable Commands on OPC Item Mode States \ \ X OPC DA Specifications_V5.1_FS20UL.
Siemens Smart Infrastructure Siemens Industry Inc. Smart Infrastructure 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000 © Siemens Industry Inc. 2021 Technical specifications and availability subject to change without notice.