Data Sheet for Product
6
Siemens Specification Texts A6V11532818_en_a_30
Building Technologies 2018-10-01
1 System description
1.1 Management level
1.1.1 Management level requirements
General
All information comes together at the management level. The management level is the graphical,
interactive interface for the operator to the automation station and the integrated plants and plant
parts.
The operator can display, query, process, save, or print any plant information via the peripheral
units at the management level. System operation must be based on a simplified approach. The
plants are displayed in synoptic images and the values and states are presented and displayed
dynamically.
Specified products: Siemens / Desigo CC Compact or similar.
System openness
The control system supports standard protocols used in building technology, including BACnet,
OPC DA (Data Access), Modbus, and S7.
Specified product: Siemens / Desigo CC Compact or similar
Exchange of data to external system via web services
The exchange of data (values, events, and trend data) between other building systems, corporate
applications, or other supplemental services, must be supported via web services.
Specified product: Siemens / Desigo CC Compact or similar
Data exchange via various subsystems
If several subsystems are used, various data must be exchanged between the automation level
(outside temperature, demand and coordination signals, etc.).
Specified products: Siemens / Desigo CC Compact or similar
System-wide self-monitoring
The system must be capable of monitoring running applications, printers, and all connected
subsystems. The system must report an event in case of an exceptional state.
Specified product: Siemens / Desigo CC Compact or similar
System analysis
Detailed analysis on system and user activities must be available in chronological order.
Specified product: Siemens / Desigo CC Compact or similar
SCADA platform
The management station must be based on a SCADA platform that is compatible with the BACnet
B-AWS profile. It must permit integration of any building installation including HVAC and lighting.
Specified product: Siemens / Desigo CC Compact or similar
Operating system for building automation and control system
All data servers, operator stations, etc., for the BAC system must be compatible with the most
current, generally available Windows 64-bit operating system. As a result, the current version of