Data Sheet for Product
14
Siemens Specification Texts A6V11532818_en_a_30
Building Technologies 2018-10-01
· Time.
· Status (acknowledged, unacknowledged).
Specified products: Siemens / Desigo CC Compact or similar
Filter alarms
The building automation and control system must offer alarm filtering. Filtering must be possible
by alarm lists or priorities. Alarms are displayed in popup windows.
Specified products: Siemens / Desigo CC Compact or similar
1.1.7 Event management
Event routing and sorting
Event messages can be displayed on each workstation in a table application and must include the
following information: Name, value, event time and date, state, priority, acknowledge information,
and alarm counter. The system must also be able to send out an acoustic message appropriate to
the event category.
Specified product: Siemens / Desigo CC Compact or similar
Event message
Event messages can be displayed on each workstation in a table application and must include the
following information on each event: Name, value, event time and date, state, priority,
acknowledge information, and alarm counter. Each event must also be able to send out an
acoustic message appropriate to the event category.
Specified product: Siemens / Desigo CC Compact or similar
Event acknowledgement
The user can acknowledge each event directly from the list, suppress the acoustic notification,
print or delete it. The interface must also have an option to deleted active, acknowledged events
until it is reset to the normal state. The user must be able to navigate to information associated
with a data point.
Specified product: Siemens / Desigo CC Compact or similar
Event treatment
The system must provide multiple alarm-handling options. These are to be configured in alignment
the standard operating procedures.
Fast Treatment
The user must be able to acknowledge each event directly from the event list, suppress the
acoustic notification, print or delete it. The interface must also have an option to deleted active,
acknowledged events until it is reset to the normal state. The user must also be able to navigate to
information associated with a data point.
Investigative Treatment
From the event list, operators shall have the ability to quickly focus on the source of the event, and
all information (recent history, schedules, and so on.) related to the event source.
Specified product: Siemens / Desigo CC Compact or similar
1.1.8 Report generation
Reports