Data Sheet for Product
11
Siemens Specification Texts A6V11532818_en_a_30
Building Technologies 2018-10-01
Specified product: Siemens / Desigo CC Compact or similar
Scheduling and override
Providing calendar type formats to simplify time and data planning and override building operation
is required. Time definitions must be located on the PC workstation and building
controller/subsystem to ensure scheduling, even if the PC is offline. Providing the following
operations at a minimum:
· Comprehensive support of all BACnet objects for scheduler, calendar, and commands.
· Daily and weekly schedules
· Ability to compile multiple data points into a logical command group to simplify scheduling
(e.g. Building 1 Lighting Group)
· Ability to plan at least 10 years in advance.
· Provide filters for schedulers by name, time, frequency, and schedule.
· Provide sorting schedulers by name and schedule type.
Specified product: Siemens / Desigo CC Compact or similar
Scheduler program types
Customized scheduler program
The user can customize the schedule defining the operating mode for each plant. Switching times
are defined via weekly schedule. Overriding recurring weekly schedules via local or global
exceptions as well as operation via any operator unit must be possible.
Specified products: Siemens / Desigo CC Compact or similar
Customized calendar
Local or global calendar exceptions must be able to override the plant-specific weekly scheduler
program. Equal calendars must be assigned priority over each other. Calendar operation must be
possible via all operator units.
Specified products: Siemens / Desigo CC Compact or similar
1.1.5 Building automation and control system operation
Multiple, concurrent users
Multiple users (up to 3) must be able to work concurrently on various workspaces on the building
automation and control system for efficient and comprehensive work. Plants must simultaneously
be analyzed and e.g. monitored or operated via a remote station.
Specified products: Siemens / Desigo CC Compact or similar
Security
The management station integrates a portfolio of products, solutions, systems and services that
includes security functions that support the secure operation of plants, systems, machines and
networks. In the field of Building Technologies, this includes building automation and control, 3
rd
party devices, and other systems.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement, and continuously maintain a holistic, state-of-the-art security concept.
The end user shall take responsibility for preventing unauthorized access to plants, systems,
machines and networks which should only be connected to an enterprise network or the internet if
and to the extent such a connection is necessary and only when appropriate security measures