Desigo CC Compact for Building Automation Specification Texts 1 Siemens Building Technologies Specification Texts A6V11532818_en_a_30 2018-10-01
Siemens Building Technologies Specification Texts A6V11532818_en_a_30 2018-10-01
Copyright Notice Notice Document information is subject to change without notice by Siemens Switzerland Ltd. Companies, names, and various data used in examples are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Siemens Switzerland Ltd.
Table of contents 1 System description ..................................................................................................... 6 1.1 Management level .................................................................................................. 6 1.1.1 Management level requirements....................................................................... 6 1.1.2 User profiles ..................................................................................................... 8 1.1.
Document Revision History Document Identification The document ID is structured as follows: ID_Language(COUNTRY)_ModificationIndex_ProductVersionIndex Example: A6Vnnnnnnnn_en_a_02 Document Revision History. Modification Index Edition Date Brief Description a 2018-10-01 Final edition for the version 3.
1 System description 1.1 Management level 1.1.1 Management level requirements General All information comes together at the management level. The management level is the graphical, interactive interface for the operator to the automation station and the integrated plants and plant parts. The operator can display, query, process, save, or print any plant information via the peripheral units at the management level. System operation must be based on a simplified approach.
Windows (at least 6 months after release by Microsoft) as well as a minimum of the last Version is supported. Modifications to the customer network must be possible. The BACS system must therefore be installable on any common PC and offer a multitasking environment where a user can run multiple applications simultaneously.
· 100 Mbps up/down · Support Wake on LAN Defined range · 1 server Max number of objects = 10,000 Specified product: SIMATIC Nanobox IPC227E Standard Hardware Small-Medium system (up to three clients) One client/server system is required for small and mid-sized sites.
than one user. The following functionalities must be by default available for the system Operator: · · · Managing of System Events (alarm management) Operate the installation via graphic application Navigate via thumbnails · · · · · Time Scheduler Trend Viewer Log Viewer Report Application Document Viewer · Remote Notifications The operating interface shall include workflow-based documentation that helps the operator to manipulate the management station. The document shall be provided in PDF format.
In graphics commanding The system must offer graphic objects which can be used to command or control the system. At a minimum, sliders, buttons, text boxes, dropdown lists and radio buttons must be included Specified product: Siemens / Desigo CC Compact or similar Visualize the quality state in the plant graphics A violation of energy efficiency limit values for measured values of primary plants (e.g.
Specified product: Siemens / Desigo CC Compact or similar Scheduling and override Providing calendar type formats to simplify time and data planning and override building operation is required. Time definitions must be located on the PC workstation and building controller/subsystem to ensure scheduling, even if the PC is offline. Providing the following operations at a minimum: · Comprehensive support of all BACnet objects for scheduler, calendar, and commands.
(e.g. firewalls and/or network segmentation) are in place. Additionally, the supplier shall provide guidance and consultation on how to implement security measures in the management level and embed protection mechanisms to prevent unauthorized accessing. Specified products: Siemens / Desigo CC Compact or similar Access Protection Multiple users must be able to maintain and operate efficiently the plant.
Alarm generation Message handling The building management system must support alarms generated at the automation level (substations). Specified product: Siemens / Desigo CC Compact or similar Alarm routing Media independent formats Current alarms may need to be routed independent of media at certain times to a central service (printer, email, SMS, pagers, and mobile apps). The number of data points that can be configured for remote messaging of alarm conditions.
· Time. · Status (acknowledged, unacknowledged). Specified products: Siemens / Desigo CC Compact or similar Filter alarms The building automation and control system must offer alarm filtering. Filtering must be possible by alarm lists or priorities. Alarms are displayed in popup windows. Specified products: Siemens / Desigo CC Compact or similar 1.1.
Report generation The system must allow generation of customized or predefined reports, to provide important plant data at any time. The reports must be printable and exportable as a PDF file. The data must be able to be edited in other programs (Microsoft Excel or Microsoft Access) for further analysis. Specified product: Siemens / Desigo CC Compact or similar Standard report templates Template to generate detailed reports at little effort. At least three different report templates must be available.
Specified product: Siemens / Desigo CC Compact or similar 1.1.10 Trend data Analyses Simultaneous, multiple trends Multiple trend views must be possible simultaneously to provide a comprehensive plant overview. Standard plants from small to medium complexity (as in this project) require a simultaneous display of up to 10 trend curves on the current page view to assess the plants. Multiple trend curves must thus be recorded at the same time.
1.2 Connectivity 1.2.1 General Interfaces The building automation and control system must be scalable to ensure long-term operation and provide all standard interfaces commonly available on today's market. Specified product: Siemens / Desigo System or similar Integrate Third-party devices via OPC The OPC Foundation must test and certify the system, which must be able to integrate and edit OPC data, and yet supply real time OPC data as an OPC server.
· Advanced reporting · · Power and Energy management Distributed system architectures · Logics and macros · Additional disciplines (e.g. Danger Management, Pharma Compliance etc.) · Unlimited clients The upgrade process shall be simple and ensure the minimum possible migration time. Specified product: Siemens / Desigo CC or similar Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 www.siemens.