User Manual
Network Security Controls
3
21
Siemens
Application Note
Smart Infrastructure
Optional Services on the main server
Component, Executable
Default Port
Port
Configuration
Protocol
-
Comment
Port exposure
Separate Web Server
3rd Party OPC Client outside Main
Server
Web Service Interface
WCCOAWsi.exe
2)
TCP: 8080 SMC
HTTP(S) - REST Web
Service
always
exposed
x
OPC DA
Siemens.Gms.OPCServer.exe
TCP: 135
UDP: 135
RPC End Point Mapping X
OPC UA: Local Discovery Server
Siemens.Gms.OPCServer.exe
TCP: 4840 OPC/TCP X
OPC UA: Local Discovery Server
Siemens.Gms.OPCServer.exe
TCP: 4883 HTTPS X
OPC UA: Local Discovery Server
Siemens.Gms.OPCServer.exe
TCP: 52601 HTTP X
OPC UA: UA Wrapper
Siemens.Gms.OPCServer.exe
TCP: 48400 OPC/TCP X
OPC UA: UA Wrapper
Siemens.Gms.OPCServer.exe
TCP: 48401 HTTP X
Desigo CC and Siveillance\Milestone
recording servers
TCP: 7563
WCF - TCP – HTTP web
services (NTLM) – Active
X
always
exposed
x
Desigo CC SiPass
TCP: 8744
TCP: 8743
TCP: 5443
API server - HTTPS
Web Service – HTTPS
Website - HTTPS
x
Desigo CC SPC
TCP: 52000
UDP: 52000
FlexC - TCP
1)
EDP - TCP
2)
EDP - UDP
3)
x
1) FlexC , TCP default port 52000, configurable, encrypted
2) EDP – TCP (for import) , default port 52000, encrypted, custom protocol.
3) EDP – UDP (only project upgrade since version 3.3), default port 52000, custom protocol.