Deployment variants: remote IIS and remote SQL Server
Component, Executable Default Port Port Configuration Protocol - Comment
Port expo-
sure
Remote
Client
Web Client
Main Server
Microsoft IIS on separate
Web Server
TCP: 80 SMC or IIS HTTP X X
Microsoft IIS on separate
Web Server
TCP: 443 SMC or IIS HTTPS X X
MS SQL Server Browser
UDP: 1434 SQL Server X
10)
sqlbrowser.exe
MS SQL Server DB instance
(HDB)
TCP: variable
3)
SQL Server X
10)
sqlserver.exe
Core Services on FEP
Component, Executable Default Port
Port
Configuration
Protocol - Comment Port exposure
PMON service
TCP: 4999 SMC
http / pmon protocol
never exposed
GMS_WCCILpmon_[ProjectName].exe
1)
Only used for communica-
tion of components on the
local machine
Directories of the host processes:
1) Located in C:\Siemens\Automation\WinCC_OA\3.15\bin\
2) Located in [Installation Directory]\GMSMainProject\bin\
Variable ports:
3) Port of a SQL Server named instance is per default variable. Refer to SQL server documentation on how to configure a fixed port
for a named instance
Consumers:
5) SMC
6) Executables on the client installation
7) Executables on the client installation
8) Executables on the FEP installation opening outbound connections
[Installation Directory]\GMSMainProject\bin\Siemens.Gms.ApplicationFramework.exe
C:\Siemens\Automation\WinCC_OA\3.15\bin\WCCOActrl.exe
Additional executables on the FEP depend on the driver type; e.g.:
BACnet: [Installation Directory]\GMSMainProject\bin\WCCOAGmsBACnet.exe
SNMP: C:\Siemens\Automation\WinCC_OA\3.15\bin\WCCOAsnmp.exe
9) Microsoft IIS
10) [Installation Directory]\GMSMainProject\bin\WCCOAHDBReader.exe
[Installation Directory]\GMSMainProject\bin\WCCOAHDBWriter.exe
[Installation Directory]\GMSMainProject\bin\WCCOAReportMan.exe
11) [Installation Directory]\GMSMainProject\bin\WCCOACoHoMngr.exe
12) C:\Siemens\Automation\WinCC_OA\3.15\bin\WCCILdist.exe