OPC Interface Specifications Version 5.1 Sintony SI400 Document No.
Siemens Smart Infrastructure SI410 intrusion detection panel This workbook describes the objects provided by the Siemens OPC Data Access Server to represent the Sintony control unit Legend ID Object Model Description
Siemens Smart Infrastructure OPC Object Specifications ID SI400-0010 Object Model Description SI410 The SI410 object represents the entire Sintony unit and the geographical area covered by the intrusion protection. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal X 7-Active 269-Activated Activated X 12-Disable \ OPC DA Specifications_V5.1_SI410.xlsx \ \ Page 3 of 13
Siemens Smart Infrastructure OPC Object Specifications ID Object Model Description SI400-0020 SI410 BACnet Device BACnet Device representing the communication characteristics of the SI410 unit. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal \ \ OPC DA Specifications_V5.1_SI410.xlsx \ \ Page 4 of 13
Siemens Smart Infrastructure OPC Object Specifications ID Object Model Description SI400-0030 SI410 Partition The partitions are a logical set of inputs. A Sintony unit supports up to 16 partitions.
Siemens Smart Infrastructure OPC Object Specifications ID SI400-0040 Object Model Description SI410 Base Object The Base Object gathers I/O transponders, Radio and Ebus gateways, card readers, and power supply.
Siemens Smart Infrastructure OPC Object Specifications ID Object Model Description SI400-0050 SI410 Bypassable Input The Bypassable Input object represents the conditions related to the Bypassable Inputs.
Siemens Smart Infrastructure OPC Object Specifications ID SI400-0060 Object Model Description SI410 Disarmable The Disarmable object represents the conditions related to all those objects that can be disarmed. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 6-Disarmed Unset 6-Disarm 1-Enable \ \ X X OPC DA Specifications_V5.1_SI410.
Siemens Smart Infrastructure OPC Object Specifications ID Object Model Description SI400-0070 SI410 Input Generic inputs are general purpose inputs. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 2-Alarm 1-Normal Alarm 8-Tamper 1-Normal Tamper 7-Active 1-Normal Activated 6-Not Ready 1-Normal Not Ready 3-Fault 1-Normal Fault 267-Non Default Mode 9-Test Test 2-Test 1-Enable \ \ X X OPC DA Specifications_V5.
Siemens Smart Infrastructure OPC Object Specifications ID Object Model Description SI400-0080 SI410 Output The Output object represents the status of the output on the Sintony unit. States Commands on OPC Item Mode OPC Item PresentValue OPC Item Mode Result State 0-Quiet 1-Normal Normal 267-Non Default Mode 9-Test Test 7-Active 9-Test Test Active X X 7-Active 1-Normal Activated X X 269-Activate 2-Test 6-Disarm 1-Enable X X OPC DA Specifications_V5.1_SI410.
Siemens Smart Infrastructure OPC Object Specifications ID Object Model Description SI400-0090 SI410 System The System object represents the possible general conditions related to the Sintony unit.
Siemens Smart Infrastructure OPC Object Specifications ID SI400-0100 Object Model Description SI410 Event commands This is not an Object Model but provides the read-only information about the event states. The event related to the point can require the acknowledge, silence/unsilence, and reset commands.
Siemens Smart Infrastructure Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd 2021 Technical specifications and availability subject to change without notice.