Desigo CC V 4.2 Advanced Reports Unrestricted © Siemens 2019 siemens.
Table of content ▪ Concept of Advanced Reports ▪ Customization of Advanced Reports ▪ Energy & Power Reports Templates ▪ Pharma Validation Report Templates ▪ Licensing of Advanced Reports ▪ Backup Information Page 2
Concept of Advanced Reporting
Desigo CC has an advance reporting engine for specific market needs Power Management Energy Consumption Pharma Customized Reports e. g.
Concept of Advanced Reports in Desigo CC Desigo CC Advanced Reports Energy & Power Report Templates Pharma / Validation Report Templates ▪ Desigo CC includes an embedded reporting engine for advanced reports. ▪ The report engine accesses trend and event data through Desigo CC web services. ▪ The report engine accesses additional data via data file (Excel) in Desigo CC Library .. Additional Report Templates* ▪ The report engine is used for all disciplines.
Reports vs. Advanced Reports in Desigo CC What is the difference? REPORTS Used for reporting collected data or data series from Desigo CC data base (online data or offline data) as table, trend or graphic Page 6 ADVANCED REPORTS Used for reporting data or data series from Desigo CC data base combined with additional: ▪ Comparisons ▪ Benchmarking ▪ Evaluations ▪ Calculations ▪ Hyperlinks ▪ Enhancements with other data e.g.
Powermanager Reports vs. Advanced Reports in Desigo CC What to choose ? Page 7 Powermanager REPORTS ADVANCED REPORTS The go to solution for Energy and Power reports Additional option to cover the following needs: - Easy set up (included in Powermanager installation) - Custom user defined calculations - 7 Energy and power reports including “Load duration curve” - Reporting based on custom hierarchies/views - Customized reports - Degree days correction.
Workflow for Advanced Reports in Desigo CC 1. Select Customer Defined View 2. Select Aggregator, Meter or Data Point to Report 3. Select Report in Application Viewer 4.
Distribution Concept for Local Client Local Installation Management System Server Installed Client (UI) LMU SMC Advanced Reports Engine Project DB WinCC OA Server Page 9 HDB SQL ▪ Advanced Report Engine must be installed on all Desigo CC Server which shall use Advanced Reports.
Distribution Concept for Remote Clients Local Installation Management System Server Installed Client (UI) SMC LMU Project DB Raima WinCC OA Server Page 10 ▪ Advanced Report Engine must be installed on all Desigo CC Server which shall use Advanced Reports. Advanced Reports Engine Web Server IIS HDB SQL Installed Client Or Web Client ▪ Access to Advanced Report for any Clients via Web Server IIS.
Distribution Concept for Multi Server / Client Local Installation Management System Server Installed Client (UI) SMC LMU Project DB Raima WinCC OA Server Local Installation Management System Server Advanced Reports Engine Web Server IIS Installed Client (UI) SMC LMU Project DB HDB SQL Raima Advanced Reports Engine Web Server IIS WinCC OA Server HDB SQL ▪ Advanced Report Engine must be installed on all Desigo CC Server which shall use Advanced Reports.
Customization of Advanced Reports Page 12
Customizing Reports What can be customized by field engineers? General Layout Settings for All Reports: ▪ Position of page number in footer [Left, Center, Right, No] ▪ Show total page number ▪ Show data and time in footer or header ▪ Name of customer ▪ Name of site ▪ Logo to display [Product Logo, Site Logo, Vendor Logo, None] Energy & Power Reports Settings: ▪ Graph type [Line Sum, Line Compare, Bar] ▪ Value display format ▪ Color selection per media group ▪ Color selection per series in chart and trend Ph
Customizing Reports What options are available for graphical representation? Bar Chart Diagram Page 14 Line Chart Diagram
Advanced Reports Templates Library
Energy & Power Report Templates 1. Comparing Consumption Report 2. Consumption Report 3. Load Profile Report 4. Max Power Report 5. Comparison Group Consumption Report 6. Consumption Node Report 7. Budget Report 8. Cost Report 9. Emission Report 10. Energy Performance Report 11. Power Usage Effectiveness Report 12. Pie Chart Consumption Report 13. Heating / Cooling Degree Days Corrected Report 14. Degree Days Regression Line Report 15. Energy Signature Report 16.
Energy & Power Reports: 1.Comparing Consumption Report Release Version: V3.0 Report compares the total consumption of a meter or a node for two configurable years against each other.
Energy & Power Reports: 2.Consumption Report Release Version: V3.0 Reports the total consumption of a meter or a node for a configurable time range.
Energy & Power Reports: 3.Load Profile Report Report provides the minimum, average and maximum power of a meter or a node for a configurable time frame. Release Version: V3.
Energy & Power Reports: 4.Max Power Report Report provides the maximum power of a meter or a node for a configurable time frame. Release Version: V3.
Energy & Power Reports: 5.Comparing Group Consumption Report Report compares the total consumption of two meter groups or nodes for a configurable time range.
Energy & Power Reports: 6.Consumption Node Report Release Version: V3.0 Reports the total consumption of all medias of a node for a configurable time range.
Energy & Power Reports: 7.Budget Report Release Version: V3.0 / EP01 Reports the consumption of meters or node compared against defined budgets.
Energy & Power Reports: 8.Cost Report Release Version: V3.0 / EP01 Reports the energy cost based on tariff data including meter fee and tax option.
Energy & Power Reports: 9.Emission Report Reports the CO2 emissions per Media on a selected node in vertical bar graph and table.
Energy & Power Reports: 10.Energy Performance Report Release Version: V3.0 / EP01 Reports the performance of energy consumption related to covered space in m 2.
Power and Energy Report: 11.
Energy & Power Reports: 12. Pie Chart Consumption Report Reports the consumption contribution of a meters or usage types for a Node and a configurable time range.
Energy & Power Reports: 13. Heating / Cooling Degree Days Corrected Report Release Version: V3.0 / EP02 Reports the consumption and degree day corrected consumption of a meter or node.
Energy & Power Reports: 14. Degree Days Regression Line Report Release Version: V3.0 / EP02 Reports the consumption against the Degree Day corrected temperature.
Energy & Power Reports: 14. Energy Signature Report Release Version: V3.0 / EP02 Reports the consumption against the outside temperature.
Energy & Power Reports: 16. Consumption and Max Power Report Release Version: V3.0 / EP02 Reports the consumption against the outside temperature.
Pharma Validation Report Templates 1. Alarm Summary Report 2. Statistic Summary MKT Report 3. Trend Chart Report (and Trend Chart Multi Axis Report) 4. Trend Table Report 5.
Pharma Validation Reports: 1.Alarm Summary Report Report displays alarm details and/or summary for the selected time range and data points. Release Version: V3.0 / EP01 Report can be used for: ▪ Any data point ▪ Aggregator / Node in user defines view Configurable Data of Report: ▪ Time range [Last, Rolling, Current or user defined] ▪ Elements to display in report [All, Graphics, Details Table, Summary Table] ▪ Alternative title of report ▪ Number of alarms (e.g.
Pharma Validation Reports: 2.Statistic Summary MKT Report Report displays alarm details and/or summary for the selected time range and data points. Release Version: V3.
Pharma Validation Reports: 3.Trend Chart Report (and Trend Chart Multi Axis Report) Report displays trend details and/or summary for the selected time range and data points with limits. The table indicates with arrows and colors when limits are reached. Release Version: V3.
Pharma Validation Reports: 4.Trend Table Report Release Version: V3.0 / EP01 Report displays trend details for the selected time range and data points in a table.
Pharma Validation Reports: 5. Audit Trail Report Report displays Audit Trail activities for the selected time range and data points in a table. Release Version: V4.
Licensing of Advanced Reports
Desigo CC Licensing of Advanced Reports Advanced Reports Advanced Reports functionality is the base line for all kind of Advanced Reports and is included in the following licenses: ▪ Desigo CC Standard Feature Set,CCA-STD-FSET, P55802-Y114-A100 ▪ Desigo CC Compact Validated Monitoring, CCA-CMPT-VM, P55802-Y121-A100 Energy & Power Reports Energy and Power Reports require managed meter functionality. The required license can be added to the Standard Feature Set (CCA-STD-FSET) only.
Backup Information
Energy & Power Reports Require Managed Meters Managed Meters are a layer on the top of consumption trend logs. Managed meters enable : ▪ Retrospective management of metering history (historization) e.g. assign a trend log to one meter for a period of time and another trend log for another period or add an offset at a specific time.
Contact Tzortzis SOROTOS Product Manager Desigo CC Siemens Schweiz AG, Building Technologies Division, International Headquarters BT CPS SRA SW MS Gubelstrasse 22 6300 Zug, Switzerland www.siemens.