4
Graphics
Overview of Graphics
44
Siemens User Guide Version 2.1 A6V10415471_en_a_21
Building Technologies 2015-07-15
Graphics Library Browser
If you have access rights for the Graphics Library Browser, you can navigate to and
display Symbols and graphic templates in the Graphics Viewer, as well as the
user’s ability to create and modify them in the Graphics Editor.
Access
If Enabled
Show
You can view Symbols and Graphic Templates in the Graphics Viewer and the
Graphics Editor.
Create
You can create new graphics, Symbols, and graphic templates, and save existing
Symbols and graphic templates.
Delete
You can delete graphics and graphic folders.
Save
You can save an existing Symbol or graphics template in its original name or in one
of the existing names in the library.
4.1.7 Scopes and Data Point Access
Assigning Scopes to Graphic Objects
Scope
is a grouping of system objects, or nodes with specific scope definitions
used for the purpose of assigning access rights. You can create scopes and assign
access rights to any of the graphic nodes in the Graphics system tree. For more
information, see Scopes.
You can apply scopes to the following graphic nodes:
Graphics
Symbols
Templates
Manual and Automatic Pages
Data Point Access Privileges
Data points are integrated into a graphic by associating them with elements. These
data points and elements can be evaluated by creating expressions that result in a
graphic that allows you to view dynamic values of a facility, building, or piece of
equipment. Data points, therefore, always display using the elements they are
associated with.
Depending on the your access rights, which are set in the System Manager, certain
data points can be inaccessible. In this case, if one or more data points associated
with an element is inaccessible, then the associated element will not display in the
graphic while in Runtime mode or in the Graphics Viewer. However, the parent of
an element, such as a Symbol instance or a group, and any other associated
children (elements), are not affected and will display on the graphic. This is
considered the
Hide-Rule
for data points in a graphic.
The
Hide-Rule
does not apply to Object References and Link Reference since
there are no COV subscriptions involved in these scenarios.
When a data point with an existing address is subscribed for COV’s, the data
point’s status and value are updated automatically in the Value Simulator view. If
the Status for the data point displays, General AccessDenied, this indicates
that the data point is inaccessible and therefore not readable for COV
subscriptions.